Read / write measuring unit „i“ (69h), Read / write timeout at bus error rs485 „j“ (6ah), N 153 – Baumer N 153 User Manual
Page 20: Example 2: change measuring unit into inches, Example 2: write parameter (time = 13.5 s)
N 153
www.baumer.com
20
Example 2: Write parameter (precision speed = 0.50; switch off point = 0.01)
SOH Adr Cmd
reserved
Precision speed =0.50
Switchoff point =0.01
EOT CRC
Transmission
01h 20h 68h 30h 30h 30h 30h 30h 30h 35h 30h 30h 30h 30h 31h 04h E0h
00
SOH Adr Cmd
reserved
Precision speed =0.50
Switchoff point =0.01
EOT CRC
Response
01h 20h 68h 30h 30h 30h 30h 30h 30h 35h 30h 30h 30h 30h 31h 04h E0h
4.3.7. Read / write measuring unit „i“ (69h)
The command is utilized to read or write the measuring unit in mm or inches.
Data = 0 (30h) = mm
Data = 1 (31h) = inch
Example 1: Read parameter (setting = mm)
SOH
Adr
Cmd
EOT
CRC
Transmission
01h
20h
69h
04h
5E
SOH
Adr
Cmd
Data
EOT
CRC
Response
01h
20h
69h
30h
04h
D0h
Example 2: Change measuring unit into inches
SOH
Adr
Cmd
Data
EOT
CRC
Transmisison
01h
20h
69h
31h
04h
D2
SOH
Adr
Cmd
Data
EOT
CRC
Response
01h
20h
69h
31h
04h
D2
Example 3: Write measuring unit mm in all SPAs by broadcast command (identifier=99)
SOH
Adr
Cmd
Data
EOT
CRC
Transmission
01h
83h
69h
30h
04h
CDh
Response
not confirmed
Important: Parameters are programmed in mm and auto-converted by SPA into inches upon displaying the po-
sition values.
4.3.8. Read / write timeout at bus error RS485 „j“ (6Ah)
This command is utilized to read or write the system time: timeout at bus error. Value range is within 00,1 s to
99,9 s. Tolerance: ±7% at minimum time; < 1‰ at maximum time, approx. 1% at 1.
Function: RS485 bus monitoring during motive shaft positioning operations. If there is no interface activity within
the programmed timeout the motor will stop (EMERGENCY OFF) upon occurring a bus error or in case of an
inactive control. A motor restart requires transmitting the profile (command „S“ or „V“) together with the start
signal (command „D“). Setting 0.00 s means function disabled.
Example 1: Read parameter (time= 2.5 s)
SOH Adr Cmd EOT CRC
Transmission
01h 20h 6Ah 04h 58h
SOH Adr Cmd
Time =2.5 s
EOT CRC
Response
01h 20h 6Ah 30h 32h 35h
04h C5h
Example 2: Write parameter (time = 13.5 s)
SOH Adr Cmd
Loop =13.5 s
EOT CRC
Transmission
01h 20h 6Ah 31h 33h 35h
04h C9h
SOH Adr Cmd
Loop =13.5 s
EOT CRC
Response
01h 20h 6Ah 31h 33h 35h
04h C9h