2 inputs, 1 analog sensor connection (sign) – Dynalco SWT-1000 Speed Switch/Transmitter User Manual
Page 5
Operating
Instructions
SWT-1000
DYNALCO
SWT-1000.r2.0609
3
Max. frequency against input voltage
0.01
0.1
1
10
100
0.001
0.01
0.1
1
10
100
1000
10000
100000
Frequency [Hz]
Input v
o
lt
a
g
e
[V
e
ff]
Trigger: 500mVpp
Trigger: 20mVeff
O.K.
NOT O.K.
2.2 Inputs
2.2.1 Analog Sensor Connection (Sign)
Frequency range (-3dB)
0.01 Hz / 35 kHz
Input impedance
30kOhm
Input voltage
• Max.
80V
rms
•
Signal
voltage [V
pp
]
0.5
1
2.5
5
10
20
Min. Pulse
width [µs]
2000
667 333 200 166 125
Minimum positive pulse
width - digital signals
Input voltage
Sensor supply
+14 V, max. 35 mA short circuit proof.
If the current limit activates, the sensor supply must be disconnected to reset the
protection.
Integrated pull-up
820 Ohm to +14V (configurable for 2 wire sensors with Jumper J1)
Trigger level
Adaptive trigger level.
Configurable with Jumper J2:
• 250mV … 6.5V (>500mVpp) [Factory configuration]
• 28mV … 6.5V (>20mV
rms
)
Screen
A terminal is provided for the sensor cable screen. This terminal is connected to the
sensor supply 0V. (0VS)
Sensor monitoring
1 of 3 settings may be configured via software:
• No
Sensor
Monitoring
• Monitoring of powered sensors
[Also for 2 wire sensors supplied via the Pull-up resistor (Jumper J1)].
Æ The sensor is considered to be defective if the sensor current consumption
falls outside of I
min
and I
max
.
I
min.
= 0.5…25mA
I
max.
= 0.5…25mA
• Monitoring of non powered sensors
[For 2 wire sensors such as electromagnetic sensors.]
Æ The sensor is considered to be defective if the circuit is disconnected.