Hardware configuration – Dynalco SWT-1000 Speed Switch/Transmitter User Manual
Page 12
Operating
Instructions
SWT-1000
DYNALCO
SWT-1000.r2.0609
10
6. Hardware Configuration
6.1 Analog Sensor Input (Sign)
Jumper
position
J1: Sensor type
J2: Adaptive trigger level
range
2 wire sensors
(with 820Ohm Pull Up resistance)
28mV to 6.5V (>20mV
rms
)
3 wire and electromagnetic sensors
(factory setting)
250mV to 6.5V
(>500mVpp)
[factory setting]
6.2 Digital Sensor Input (IQ)
No hardware configuration necessary.
J1
J2