beautypg.com

Dynalco SWT-1000 Speed Switch/Transmitter User Manual

Page 17

background image

Operating

Instructions

SWT-1000

DYNALCO

SWT-1000.r2.0609

15


7.5.4 Limits (Configuration

Æ Limits)

The SWT-1000 series offers 2 independent limits

Æ Limit 1 and 2.

Status

Limits are selected here. If the limit is deactivated, the other values such as set points and mode
have no further effect.

Mode

In Normal Mode the limit is active as soon as the High set point is exceeded. In Inverse Mode the
limit is active from the start (zero speed) and deactivates when the set point is reached (Fail Safe
operation)

Upper and Lower Setpoint

RPM

limit

activated

deactivated

lower

switching point

upper
switching point

As the speed increases, the limit switches when the High set point is reached and remains in that
condition until the speed reduces past the Low set point.

7.5.5 Relay Parameter and Selection of Parameter Set
(Configuration

Æ Relay control)

Parameter set A / B selection

With standard factory setting, parameter set B may be activated via the binary input B1>. If parameter set B is to be deactivated, this setting should be none (always control A)

Delay time when switching A <- B

This value determines the delay from switching the binary input to the switching from parameter
set B to parameter set A.

Relay assignment with control A

Defines the relay behavior in parameter set A.

Relay assignment with control B

Defines the relay behavior in parameter set B.

Relay

Defines the source information for relay switching.

Status
register

Relay dependency

Alarm

(Common) Alarm [7.5.1 System Parameters (Configuration

Æ

System)]

Sensor monitor

Sensor status (7.5.2 Sensor Parameters (Configuration

Æ

Sensor))

Limit 1/2

Selection of Limit ½ (
7.5.4 Limits (Configuration

Æ Limits)

Window

ExOR combination of both limits

On

The relay is on

Off

The relay is always off

Acknowledge

Acknowledge establishes if and under what conditions the relay status is held. A relay that is held
no longer reacts to the assigned signal and can only be reset via the binary input.