4 parameter list and ranges, 5 parameters – Dynalco SWT-1000 Speed Switch/Transmitter User Manual
Page 14
Operating
Instructions
SWT-1000
DYNALCO
SWT-1000.r2.0609
12
7.4 Parameter List and Ranges
If you already have a configuration file you can open and view it using the SWT-1000 Windows
Software menu
File
Æ Open
You can also connect the SWT-1000 to a PC (see section 7.2) and read back the parameters,
SWT-1000
Æ Read parameters
Once loaded into the software the parameter set may be printed via File
Æ Print
Normal Windows file handling rules apply.
7.5 Parameters
Parameters are changed in the sub menus from the drop down menu “Configuration“. Parameter
list and ranges. Factory settings are shown in bold.
Configuration < System >
Machine factor
1.0000E-07 ... 1.0000 ... 9.9999E+07
Minimum Measuring time
2 / 5 / 10 / 20 / 50/ 100 / 200 / 500 ms / 1/ 2 / 5 Seconds
Min displayed measured value
1.0000E-12 ... 1 ... 1.0000E+12
Alarm definition
Only System error System error OR Sensor Monitoring
Configuration < Sensor >
Sensor Type
Active / Passive
Sensor input
Analog (Sign) / Digital (IQ)
Sensor current minimum
0.5 ... 1.5 ... 25.0mA
Sensor current maximum
0.5 ... 25.0mA
Configuration < Analog output >
Measuring range start value
0.0000 ... 90% of the end value
Measuring range end value
1 … 2000.0 … 500000
Output range
0 ... 20mA / 4 ... 20mA
Time constant (Damping)
0.0 ... 9.9s
Configuration < Limits >
Status Limit
1
On / Off
Status Limit
2
On / Off
Mode Limit
1
Normal / Inverse
Mode Limit
2
Normal / Inverse
Lower Set point
Limit 1
0.1 … 200.00 … 500000
Upper Set point
Limit 1
0.1 … 300.00 … 500000
Lower Set point
Limit 2
0.1 … 400.00 … 500000
Upper Set point
Limit 2
0.1 … 500.00 … 500000
Configuration < Relay control >
Switching of control A/B
Selection of actuator
None (always control A) / Binary Input B1
Delay time
0 ... 2.000 s
Relay Assignment
Control
A
Alarm / Sensor monitor / Limit 1 / Limit 2 / Window / On /
Off
Acknowledge A
Without acknowledge (no hold function) /
Relay held when control active /
Relay held when control inactive
Acknowledge B
Alarm / Sensor monitor / Limit 1 / Limit 2 / Window / On /
Off
Acknowledge B
Without acknowledge (no hold function) /
Relay held when control active /
Relay held when control inactive