Control Panel
Vacuum System
Accessories
Vacuum Pump
Air Receiver
• UL listed digital control panel in a NEMA 12 enclosure with a
5.7” Touch Screen Display
• Only panel components that are commercially available and
not of propriety design will be considered
• Our pumps include the following accessories:
- Temperature sensor at each discharge port of the pump
with numerical display
- Externally operable circuit breakers with door interlock
per pump
- Control circuit transformers with fused primary and
secondary circuit breakers
- WinCE 5.0 operating system
- Illuminated H-O-A switch
- Magnetic starter with three leg overload protection
- Hour meter and motor running light
• Audible and visual local alarms with dry contacts for the
following:
- Lag pump in use
- High discharge air temperature
- Main transformer failure
- Motor overload
• Provide manual reset for all alarms
• All control and alarm functions shall remain energized while
any pump in the system remains electrically on-line
• Ethernet connectivity with embedded web-page for remote
monitoring, password protected remote adjustment of all
operating parameters
• Lag pump shall be able to start automatically if the
lead pump fails to operate
• Alarm contacts will be provided for remote annunciation for
all alarm points
• Shutdowns for systems are as per NFPA
• Vacuum pump shall be an Oil-Less Rotary Vane type and
operate completely dry with air cooled design
• Shall be equipped with self-lubricating carbon or graphite
vanes with no water requirements
• Bearings shall be permanently lubricated and sealed
• Vacuum pump shall be direct driven
• Torque is transmitted from the motor to the pump
through a shaft coupling
• Each vacuum pump shall have a factory piped intake with
integral flex connector, isolation valve, and check valve
• Each pump shall have a built-in anti-suck back valve
mounted at the pump inlet
• Each pump shall be direct driven through a shaft coupling
by a NEMA C-face, TEFC electric motor
• System should also have a means of removal of the
vacuum pump for service or replacement without
interruption to the system
• The pump shall include:
- An inlet air filter (optional)
- Flexible connectors
- Isolation valve
- Check valve
- High discharge temperature
sensor (with visual indicator)
• Shall be ASME certified with provisions for isolating the
receiver without interruption of the vacuum service
• Receiver shall be rated for full vacuum service with a minimum
200 psig design pressure
• Shall be equipped with a vacuum gauge, manual drain valve,
and a shut-off valve
• The inside consists of a two-part epoxy coating providing rust protection equal
or better than that achieved by galvanizing
Amico Source | 85 Fulton Way, Richmond Hill, ON, L4B 2N4, Canada Toll Free Tel: 1.877.462.6426 | Tel: 905.764.0800 | Fax: 905.764.0862
www.amico.com
M
²)
M²
M²
M²
M²
M²
M²
- NFPA Triplex RVD Modular Stack Mount NFPA Triplex CCD Modular Stack Mount NFPA Quadruplex RVL Modular Stack Mount NFPA Quadruplex RVD Modular Stack Mount NFPA Quadruplex CCD Modular Stack Mount NFPA Duplex RVL Vertical Tank Mount NFPA Duplex RVL Modular Stack Mount NFPA Duplex RVL Horizontal Tank Mount NFPA Duplex RVD Vertical Tank Mount NFPA Duplex RVD Modular Stack Mount NFPA Duplex RVD Horizontal Tank Mount NFPA Duplex CCD Vertical Tank Mount NFPA Duplex CCD Modular Stack Mount NFPA Duplex CCD Horizontal Tank Mount