beautypg.com

Amico NFPA Triplex RVL Modular Stack Mount User Manual

Page 18

background image

Amico Source Equipment

1.

Control Panel Features:

Only panel components that are commercially available and not of propriety design will be considered.

a.

NEMA 12 control panel enclosure.

b.

Full voltage motor starter shall be UL 508 E self-protected combination starters with

overload protection and external operators.

c.

Door interlock disconnect switch.

d.

90 dB alarm buzzer.

e.

Visible indicator of “power on” and “pump running” for each pump.

f.

Two control transformers with secondary circuit breaker.

g.

Manual / Off Auto selector switches (Each Pump).

h.

Transducer and RTD based controls.

i.

The RTD will digitally display the running temperature of each discharge port and shall be

field set table to standard manufacturer’s operating parameters.

j.

The calibration of the pressure transducer can be set so a non-standard transducer can be

used.

2.

Touch screen controls feature a minimum 5.7” screen. Screen displays and functions include:

a.

WinCE 5.0 operating system.

b.

OPC, TCP/IP and Communication drivers.

c.

Ethernet connectivity with embedded web-page for remote monitoring, multi-level

password protected for remote adjustment of all operating parameters.

d.

Electronic notifications of alarms and warnings.

e.

Communication expansion capability to talk over five Networks/Protocols.

f.

Service alerts, runtime for each pump, system status, system vacuum level all shall be

displayed.

g.

Visual/audible indications with isolated voltage free contacts for all alarms.

h.

Event log recording of alarms and system activity.

i.

Event log recording of service warnings and service history.

j.

Trend graphs for all vacuum level, pump operations, and ambient temperature.


k.

Adjustable settings to accommodate user needs.

16