APPENDIX B – SCR200 TROUBLESHOOTING

SYMPTOM

POSSIBLE

CAUSE

EXPLANATION / ACTION

No Display

No AC Power

Check Input Power. Check Breaker. Mains fuse on Control Board

F01

Deeply

Discharged

Battery

Battery Voltage less than 1.9 volts per cell initially but rose above this

level within the first minute. Check battery condition and Equalize.

F02 Over

discharge

Battery less than 1.9 volts per cell after the first minute of charge. Check

battery condition and Equalize

F03 Sulphated

Battery

Make sure your battery gets a full charge every cycle. Check battery

condition and Equalize.

F04

Charger

Overheating

Check Fan for operation on initial power up. Ensure adequate

ventilation. Contact your local

GNB Industrial Power

representative.

F05

Mains Failure

Electrical Supply failure during charge. (Power Cut)

F06

No Output

Current

Check DC Fuse, SCRs. Connection to Battery.

Incorrect Battery

Make sure the battery voltage matches the charger voltage.

Low Voltage

<1.70 vpc

Check battery voltage with a voltage meter. Make sure battery voltage

matches charger. Battery may require servicing.

F07

High Voltage

>2.25 vpc

Check battery voltage with a voltage meter. Make sure battery voltage

matches charger.

F09 Battery

Failure

Battery did not reach gassing volts within the time limit.

Check battery for low voltage. Confirm charger capacity is correctly

matched to battery. Check battery condition.

Contact your local

GNB Industrial Power

representative.

F10

Second Stage

Time-Out

I2 limit not reached within time limit. Check battery condition.

Contact your local

GNB Industrial Power

representative.

F11

Incorrect Mains

Frequency

Check the mains supply.

F12

Board

Failure

Contact your local

GNB Industrial Power

representative.

F13

Temperature

Sensor Failure

Contact your local

GNB Industrial Power

representative.

F17

Auto Balance

Stage Time Out

Check battery condition.

F16

Battery

Overheating

Check battery for High Temperature. Allow battery to cool. Check battery

condition. Confirm charger capacity is correctly matched to battery

F18

Battery

Disconnection

Press the PAUSE button before disconnecting the battery.

F19

Battery

Disconnection in

Cool Down

Allow the battery to cool before use.