The DC charging cable has a commonly used battery plug or receptacle. The polarity
of the charger plug must be the same as the battery connector. The BLACK DC
cable must be connected to the battery negative terminal (-) and the RED DC cable
must be connected to the battery positive terminal (+). The charger will not operate in
a reversed polarity condition. The DC output fuse is a “fast-acting” fuse used to
protect the power semiconductors of a charger.
NOTE:
Use only identical replacement fuses available from your GNB Industrial Power
service representative. The DC fuse must be replaced with a fast acting fuse
capable of protecting semiconductors. See Appendix C and D for correct fuse
sizes.
8. FAULT
AND
DISPLAY
CODES
Refer to Appendix A and B (on pages 16 and 17) for a complete list of fault codes.
9. OPTIONS
9.1 JIC SWITCH ASSEMBLY
All SCR200 battery chargers can come with a factory installed JIC switch assembly
option for extra operator protection. In the "OFF" position, the door can be opened
but only AC power at the input of the switch is present while everything downstream
is dead. In the "ON" position, AC power is supplied to the charger but the door
cannot be opened.
9.2 MOMENTARY REMOTE STOP OPERATION
The SCR200 charger has a complete remote control option, which can be factory
installed or field retrofitted. Contact your local GNB Industrial Power representative
for more details.