11.5 AUTO BALANCE

The charger maintains a current equal to 19% of the maximum output that is

activated by voltage, on at 2.15VPC and off at 2.35VPC with a time limit of 2 hour if

2.35VPC is not reached. The Liberator® profile is 22% of maximum current output,

on at 2.2VPC and off at 2.4VPC, Time limit of 2 hours.

When current is flowing, amps will be displayed and the yellow LED will be

illuminated. When no current is flowing, the display will show ‘StSt’. The FUNCTION

button can select charge information. The green LED will remain illuminated.

11.6 EQUALIZE STAGE

Equalize charge provides 19% of maximum current for 3.5 hours. The Liberator

profile is 22% of the maximum current for 12 hours.

The following table summarizes the action taken when Equalize is set manually

during different charge modes…

Charge Mode

Action

During recharge

Equalize active after termination

After charge termination Equalize active immediately

Smart Start termination Equalize active after termination

11.7 EQUALIZE PUSHBUTTON

Equalize charge can be enabled/disabled, when the FUNCTION button is depressed

> 5 second at anytime whilst a battery is connected. Only one equalize charge per

recharge cycle is permitted. The equalize charge can be set in the service mode to

be initiated at ‘x’ number of cycles. X = 0 to 255.

CAUTION:

DO NOT EQUALIZE MORE OFTEN THAN REQUIRED BY THE
CONDITION OF THE BATTERY, AS SPECIFIED IN THE BATTERY
MAINTENANCE INSTRUCTIONS. EXCESSIVE EQUALIZING MAY
DAMAGE THE BATTERY.

11.8 LOW BATTERY OVERRIDE/RECOVORY

11.8.1 CONFIGURATION

There is the ability to manually override the low ‘Incorrect Battery’ threshold of

1.70 VPC, down to a minimum of 1.00 VPC - the level at which the charger will

recognize a battery connection. This is achieved by holding the FUNCTION

push button for 5 seconds when the incorrect battery fault has been detected.

11.8.2 OPERATION

If ‘Low Battery Override’ has been enabled and a battery (voltage > 1.00 VPC)

is connected to the charger, the charger will pass current at 75% of maximum

current output the charger rated output current level.