2. OPERATION
2.1. 046-0172 CONTROL
The charger utilizes a
controlled ferro-r esonant transformer , whi ch prov ides
isolation fro m the AC service lin e and regulates the charging current. The
transformer output is connected to a full- wave bridge of silicon diod es, which
provides DC charging current to the battery.
The starting charge amps and length of time required for a charge vary depending
on the charger m odel, a nd si ze of batt ery. See th e data plate o n the cha rger for
specific information.
2.1.1. FEATURE SUMMARY
•
Automatic start when the battery is connected, or manual start (if selected).
•
Automatic stop when charge is finished.
•
Fully charges partially discharged batteries without overcharging.
•
Dead battery ‘jump start’ for overly-discharged batteries.
•
Equalize charge by user request.
•
Automatic shut-down if battery starts to overheat.
•
Automatically resumes charge after a power failure during the charge cycle.
•
Displays charging amps, battery volts/cell, full battery voltage, amp-hours returned, and run time.
•
Delayed start adjustable from 1 minute to 24 hours.
•
Delayed start until a certain time-of-day.
•
Automatic equalize by number of charges.
•
Automatic equalize by day-of-week.
•
Charge indication codes with descriptive messages.
•
Cool down timer adjustable from 1 minute to 24 hours.
•
Periodic alert messages describing charger status.
•
Compatible with the Tobi® Battery Management System.
TOBi® is a registered trademark of Ferro Magnetics Corporation, St. Louis, Missouri
CAUTION: If the battery must be disconnected before the end of the charge cycle, the charger