Ferro Magnetics Corporation, St. Louis, MO
575
POWER TRANSFORMER SETTING
480
L2
L2
1 2 3 4 5 6
1 2 3 4 5 6
L1
L1
1 2 3 4
1
3
2
4
CONTROL
TRANSFORMER
CONTROL
TRANSFORMER
1.3. LINE VOLTAGE ADJUSTMENTS
All chargers are shipped with the AC line voltage ju mper wires set for the AC voltage spe cified on the
purchase order. Before connecting the charger to the AC service, it should be verified that the internal AC
voltage connections match the available AC service voltage. If necessary, change the AC voltage jumper
wires as shown in Figs. 1.3.1 through 1.3.2.
CAUTION:
It will be necessary in most cases to change the AC fuses when the AC voltage
jumpers are changed. Refer to the fuse chart on the inside door of the charger for the correct fuse
rating.
Fig. 1.3.1.
A.C. Voltage Adjustments
1Ø & 3Ø 60Hz. (208/240/480)
“B” Voltage Code
Fig.1.3.2.
A.C. Voltage Adjustments
3 Ø 60Hz. (480/575)
“K” Voltage Code