2.1.10.10. DISPLAY TIME OF DAY
To view the current time, press ‘CLO CK. The DATA display shows the time-of-day in 24-hour format. The
UNITS display shows ‘HM’ for hours and minutes format.
2.1.10.11. DISPLAY COOL-DOWN TIME
To view battery cool do wn time, p ress ‘CO OL DO WN’. The DATA di splay shows th e cool do wn time
setting in hours and minutes. The UNITS display will show ‘HM’ for hours and minutes format.
2.1.10.12. DISPLAY PERCENT AMP-HOURS RETURNED
To view amp -hours retu rned a s a p ercentage of th e battery size pre ss ‘% RET’N’. The DATA display
shows the percentage of amp-hour capacity returned. The UNITS display will show ‘%’ for percentage.
2.1.10.13. DISPLAY TRIP POINT
To view the cell voltage at which the battery is 80% charged, press ‘TRIP POINT’. The DATA display will
show the 80% voltage as volts per cell. The UNITS display shows ‘VC’ for volts per cell.
2.1.10.14. PERFORM LAMP TEST