beautypg.com

9 gas-tight design (option), 10 signal transmitter (option), Blocking screw (option) – Richter KSE-C/F Series Safety Valves User Manual

Page 11: Gas-tight design (option), Signal transmitter (option), Series kse/f, kse-c/f, 8 blocking screw (option), 9 gas-tight design, 10 signal transmitter

background image

Series KSE/F, KSE-C/F

Page 11

9530-050-en

Revision 04

TM 7489

Edition 03/2009

6.8 Blocking screw (option)

During the pressure test of the plant the safety valve

cannot discharge through the blocking
screw.

This blocking screw may only be used for
this purpose. Always remove again

immediately.
Damage to the valve could occur and pressure
protection is then no longer provided.
The lead-sealed cap nut 927/1 is replaced during
the pressure test of the plant by a cap nut 927/1B
with an additional tapped bore
for the blocking
screw 901/4.
In the KSE/F 100/150 the lead-sealed hex. screw
901/3 is replaced by a threaded rod 918/1 with a
prevailing torque type hex. nut 929/2.
The

cap

nut/blocking

screw

or

the

threaded rod/hex. nut are supplied separately.
See also the details in Fig. 5.
After the pressure test remove the cap
nut 927/1B with the blocking screw 901/4
or threaded rod 918/1 with the hex. nut
929/2 again.
Screw in the cap nut 927/1 or, in the case of the
KSE/F 100/150, the hex. screw 901/4 with the bore
for the lead seal again and have them lead-sealed
again
. See also Fig. 6.

DN 100/150

DN 80/100

Legend see Section 10.1

Fig. 6

6.9 Gas-tight design

(Option)

An O-ring 400/4 seals the lifting lever 238.

Fig. 7

Legend see Section 10.1

6.10 Signal transmitter

(Option)

On request, an signal transmitter is available for
remote monitoring.

Glue in stem extension 805 (e.g. Loctite 638) and
secure with a hex. nut 920/4.
The support, lower part, 542 is screwed on instead
of the cap nut 927/1.
Insert the O-ring 400/3.
Mount support, upper part, 541.
Screw in signal transmitter 859; after adjustment,
counter with hex. nut.
Secure support, upper part, with setscrew 904/1.
Design with blocking screw:
Insert the O-ring 400/2, screw in hex. screw 901/4
and lead-seal. See Fig. 10.

DN 25/50, 50/80, 80/100

Fig. 8

DN 100/150

Fig. 9