9 annex, 1 technical specifications, General data – Richter SAFERUN User Manual

Page 17: Power supply (non-potentially explosive area), Power supply (potentially explosive area), Inputs, Outputs note see section 1.4, Technical specifications, Outputs, Note see section 1.4

background image

Series MNK, MNK-B,

SAFERUN

®

Pump condition monitoring system

Page 17

9230-070-en

Revision 01

TM 7691

Edition 11/2009

9

Annex

9.1 Technical specifications

GENERAL DATA

Manufacturer

Richter Chemie-Technik GmbH

Unit

Condition monitoring system

Type

4764-19-0020/02

Technical documentation

BTA 9230-020-de.

Design

Unit for mounting on pumps or for wall mounting (cable of
special length required)

IP protection class (EN 60529)

IP 65

Housing material

ABS, modified (surface resistance 10

6

)

Tension spring terminals

Max. line cross section 1.5 mm

2

POWER SUPPLY (non-potentially explosive area)

Power supply

DC 16 ... 30 V

Cable connection

3-wire, with shield

POWER SUPPLY (potentially explosive area)

Supply and feed circuit and signal cir-
cuit (from 3-wire circuit)

Of ignition protection class "Intrinsically safe" with the max.
input values:
U

i

28 V; I

i

120 mA; P

i

750 mW

Ignition protection class: (gas explosion

protection)

(dust explosion protection)

II 2 G Ex ib IIB T4...T6

II 2 D Ex ibD 21 T 130 °C

Max. adm. ambient temperature range

for applications in T6 : - 20 °C T

a

40 °C

and

for applications in T4 : - 20 °C T

a

60 °C

Cable connection

3-wire, with shield

INPUTS

Sensor unit

SAFERUN

®

can, type 9237-31-3201/3

Magnetic field sensor (max. values)

U

o

5.88 V and I

o

11.88 mA and P

o

17.46 mW

Temperature sensor (max. values)

U

o

5.88 V and I

o

15.94 mA and P

o

23.28 mW

Cable

5-wire, twisted with shield, max. length = 5m

Radio transmission (RFID)

RFID transponder (passive)

Frequency range

13.56 MHz (HF)

Memory

256 kbit EEPROM

Transmission rate

106 kbps

Writing/reading range

up to 30 mm

Mobile writing/reading units

PDA with CFC reader (RFx10-Ex/AM)
(also available in non-potentially explosive design)

Serial interface
(programming adapter)

RS232 (only accessible by opening the housing)

Connection cable

PROG-CABLE- SAFERUN

®

with USB 1.1 connection

Communication unit

PC or laptop with USB connection

Special feature

Power supply is possible via integrated set-up transformer

Note on explosion protection

Not suitable for use in potentially explosive area

OUTPUTS

Note see Section 1.4

Analog

4 ... 20 mA

HART

Temperature, speed, performance, flow rate