2 condition monitoring and event display, 1 leds, Condition monitoring and event display – Richter SAFERUN User Manual
Page 10: Leds, Series mnk, mnk-b, Saferun, Pump condition monitoring system
Series MNK, MNK-B,
SAFERUN
®
Pump condition monitoring system
Page 10
9230-070-en
Revision 01
TM 7691
Edition 11/2009
6.2 Condition monitoring and
event display
Note:
see Section 1.4.
The monitoring mode is the normal mode of the
SAFERUN
®
. In this mode the following conditions can
be detected and displayed by the system:
Operation within the recommended operating
limits:
Direction of rotation:
Is determined every time the pump is put into op-
eration.
Qmin reached:
Basic setting: Q/Q
opt
= 8%
Qmin undershot:
The minimum flow rate Q
min
recommended by the
manufacturer is undershot; continuous operation in
this condition can result in damage to parts of the
pump.
Qmax reached:
Basic setting: Q/Q
opt
= 120%
Qmax exceeded:
The maximum value of the flow rate Q
max
recom-
mended by the manufacturer is exceeded; con-
tinuous operation in this condition can result in
damage to the pump.
Zero conveyance/Lack of lubrication:
At this operating point safe operation of the pump
can no longer be guaranteed; in this case the
flushing circuit and the lubrication of the bearings
may be suddenly interrupted by overheating and
evaporation of the enclosed medium.
Sudden condition change:
Basic setting: Fluctuations of more than 20% of the
design torque (Q
opt
)
Drive stoppage:
In operation with overloaded magnetic drive …not
admissible --- switch off immediately.
6.2.1 LEDs
Start:
All displays come on
Cold start 5 seconds
Warm start 3 seconds
Self-test:
If error, error position flashes (A-G or
temperature sensor)
Temperature sensor
flashing
Line interrupted
fast flashing
Short circuit or off
Sudden load change
flashing
Shortly before max. loading of
the magnetic drive
fast flashing
Drive stoppage
Direction of rotation
both flashing
No connection
Cable missing
both come on
Pump at standstill
green comes on
Clockwise
red comes on
Counterclockwise
Fig. 9
Flash when there is an error:
A
RAM
Main memory defective
B
ROM
Firmware defective
C
Clock
System time is wrong
D
FRAM
Data loss/defective
E
RFID
Data loss/defective,
not connected
F
Parameters
not present or defective
G flashing Performance curves not available
G
faster flashing Value error
A B
C
D
E
F G