• For a venting system that extends through

any zone above that on which the connected
appliance is located (except for one and two
family dwellings), the vent system shall be
enclosed with an enclosure having a fi re
resistance rating equal to or greater than that of
the fl oor or roof assemblies through which it
passes.

• Design any enclosure to permit inspection of the

system.

• Do not place any type of insulation in any

required clearance spaces surrounding the vent
system.

6. Vertical Installation Requirements:

a. Seal weather exposed joints of the outer jacket

with foil tape or an exterior grade silicone
sealant.

b. The vent system must terminate at least 3 feet

above the roof line and at least 2 feet higher than
any portion of the building within 10 feet.

c. When terminated at a height of more than 6 feet

the stack must be supported by a support bracing.
The vent should be supported every 10 feet.

d. The total continuous distance of the vent system

from the appliance fl ue collar to the termination
shall not exceed that specifi ed in the appliance
manufacturer’s installation instructions.

e. In cold climates do not install a condensate drain

on the exterior of the building. Doing so may
result in dangerous icy conditions on surfaces
near the drain and may cause damage to the vent
system and/or the building exterior.

f. Install supports every 10 feet vertically along the

vent pipe route. Vertical supports are required
after every transition to vertical and are required
after every offset elbow. When the vent is free
standing and penetrates a roof/ceiling another
means of support must be used at a second
location. Refer to the Vertical Supports section
in this manual.