Watts R44-24-1111000 User Manual
Page 27
VI. APPENDIX
The following tables are intended as a guide to determining the flow rates for the R44
series RO systems. All flows are in gallons per minute (GPM).
Nominal flows for systems without reject recycle
and a feed water Silt Density Index less than 3.
R44-16
R44-20
R44-24
Product (max)
20
25
30
Reject
10.8
13.5
16.2
Nominal flows for systems with reject recycle
and a feed water Silt Density Index less than 3.
R44-16
R44-20
R44-24
Product (max)
20
25
30
Reject 6.7
8.4
10
Reject Recycle
4.1
5.1
6.2
Nominal flows for systems without reject recycle
and a feed water Silt Density Index of 3 to less than 5.
R44-16
R44-20
R44-24
Product (max)
18
22.5
27
Reject
9.7
12.1
14.5
Nominal flows for systems with reject recycle
and a feed water Silt Density Index of 3 to less than 5.
R44-16
R44-20
R44-24
Product (max)
18
22.5
27
Reject 6
7.5
9
Reject Recycle
3.7
4.6
5.5