APPLICATION DATA (cont)

EVAPORATOR-FAN MOTOR PERFORMANCE

UNIT

EVAPORATOR-FAN

MOTOR

UNIT

VOLTAGE

MAXIMUM

ACCEPTABLE
CONTINUOUS

BHP*

MAXIMUM

ACCEPTABLE

OPERATING

WATTS

MAXIMUM

AMP DRAW

558D036

Standard

208/230

0.34

440

2.9

460

1.4

575

1.4

Alternate

208/230

1.00

1000

5.1

460

2.3

575

2.3

558D048

Standard

208/230

0.75

850

3.7

460

1.9

575

1.9

Alternate

208/230

1.00

1000

5.1

460

2.3

575

2.3

558D060

Standard

208/230

1.20

1340

6.2

460

3.4

575

3.4

Alternate

208/230

1.80

1921

6.1/9.2†

460

2.7

575

2.7

558D072

Standard

208/230

2.40

2120

6.1

460

2.7

575

2.7

558D090

Standard

208/230

2.40

2120

6.1

460

2.7

575

2.7

558D102

Standard

208/230

2.40

2120

6.1

460

2.7

575

2.7

558D120

Standard

208/230

2.40

2120

6.1

460

2.7

575

2.7

Alternate

208/230

2.90

2615

7.9

460

3.6

575

3.6

558D150

Standard

208/230

4.20

3775

12.6

460

5.7

575

5.7

Alternate

208/230

5.25

4400

15.0

460

7.4

575

7.4

559F180

Standard

208/230

4.25

3775

10.5

460

4.8

575

3.45

3065

3.9

559F216

Standard

208/230

5.90

5180

15.8

460

7.9

575

6.0

559F240

Standard

208/230

8.70

7915

25.0

460

9.50

8640

13.0

575

8.70

7915

10.0

559F300

Standard

208/230

10.26

9510

28.0

460

11.80

11,000

14.6

575

10.26

9510

13.0

LEGEND

BHP — Brake Horsepower

*Extensive motor and electrical testing on these units ensures that the full horsepower range of the motors can be

utilized with confidence. Using your fan motors up to the horsepower ratings shown in this table will not result in
nuisance tripping or premature motor failure. Unit warranty will not be affected.

†Single phase/3 phase.