FAN RPM AT MOTOR PULLEY SETTINGS*

UNIT

MOTOR PULLEY TURNS OPEN

0

1

2

1

1

1

2

2

2

1

2

3

3

1

2

4

4

1

2

5

5

1

2

6

558D036†

1000

976

952

928

904

880

856

832

808

784

760

558D048†

1185

1150

1115

1080

1045

1010

975

940

905

870

835

558D060†

1300

1260

1220

1180

1140

1100

1060

1020

980

940

900

558D072**

1460

1420

1380

1345

1305

1265

1225

1185

1150

1110

1070

558D090**

840

815

790

765

740

715

690

665

635

615

590

558D090††

935

910

885

860

835

810

785

760

735

710

685

558D102**

935

910

885

860

835

810

785

760

735

710

685

558D120**

935

910

885

860

835

810

785

760

735

710

685

558D120†

1085

1060

1035

1010

985

960

935

910

885

860

835

558D150**

1080

1060

1035

1015

990

970

950

925

905

880

860

558D150†

1260

1220

1185

1155

1130

1100

1075

1045

1015

990

960

930

900

559F180,

208/230,

460 V**

1559

1524

1491

1458

1425

1392

1359

1326

1293

1260

1227

559F180,

575 V**

1462

1436

1410

1384

1358

1332

1305

1279

1253

1227

1201

559F216**

1251

1234

1217

1200

1183

1166

1149

1132

1115

1098

1081

1064

1047

559F240**

1494

1473

1451

1430

1409

1387

1366

1345

1323

1302

1281

1259

1238

559F300**

1536

1515

1494

1472

1451

1430

1408

1387

1366

1344

1323

*Approximate fan rpm shown.

†Indicates alternate motor and drive package.

**Indicates standard motor and drive package.

††Indicates alternate drive package only.

Do not run this fan at less than 1 full turn open, as it will exceed the maximum allowable rpm of 1550.

OUTDOOR SOUND DATA (Total Unit)

UNIT

SOUND RATING

(Bels)

A — WEIGHTED

(db)

SOUND POWER (db)

Octave Bands

63

125

250

500

1000

2000

4000

8000

558D036-060

8.2

80.5

56.8

75.8

72.4

72.9

74.8

75.4

71.3

69.1

558D072

8.4

82.4

56.0

69.8

72.9

75.9

78.3

76.5

72.6

67.9

558D090,102

8.6

86.4

83.2

87.4

83.5

82.8

83.0

77.7

71.8

67.0

558D120

8.8

87.6

97.6

90.4

85.7

84.8

83.9

77.5

71.3

65.8

558D150

8.8

86.4

83.7

87.2

83.4

82.8

83.0

77.7

71.8

67.0

559F180

8.8

87.3

87.1

89.9

86.4

84.0

82.7

79.0

73.9

68.6

559F216

9.0

89.5

95.7

88.9

87.2

85.2

81.9

79.5

72.7

65.0

559F240

9.5

94.1

98.7

92.3

93.8

90.9

89.6

85.9

80.3

74.3

559F300

9.5

94.1

98.7

92.3

93.8

90.9

89.6

85.9

80.3

74.3

Bels — Sound Levels (1 bel = 10 decibels)
db

Decibels

ELECTRIC HEAT MULTIPLICATION FACTORS

HEATER

VOLTAGE

ACTUAL HEATER VOLTAGE

200

208

230

240

280

440

460

480

550

575

600

240

0.694

0.751

0.918

1.000

480

0.626

0.840

0.918

1.000

575

0.915

1.000

1.089

NOTE: The following equation converts kW of heat energy to Btuh:
kW × 3.412 = Btuh.

EXAMPLE: 32.0 kW (at 240 v) heater on 208 v = 32.0 (.751 mult factor)

= 24.0 kW capacity at 208 v.

48