AIR DELIVERY — 558D036-150 HORIZONTAL DISCHARGE UNITS

558D036 (3 TON)

Airflow

(Cfm)

Standard Direct-Drive Motor

Low Speed

High Speed

208 v

230, 460, 575 v

208 v

230, 460, 575 v

ESP

Bhp

Watts

ESP

Bhp

Watts

ESP

Bhp

Watts

ESP

Bhp

Watts

900

0.72

0.21

253

0.75

0.23

277

0.73

0.26

307

0.76

0.31

363

1000

0.67

0.23

270

0.69

0.25

292

0.70

0.27

321

0.71

0.32

374

1100

0.61

0.24

287

0.63

0.26

307

0.64

0.28

335

0.65

0.33

385

1200

0.57

0.26

304

0.58

0.27

323

0.56

0.29

349

0.59

0.34

397

1300

0.51

0.27

321

0.53

0.29

338

0.53

0.31

364

0.54

0.34

408

1400

0.44

0.29

338

0.46

0.30

354

0.47

0.32

378

1500

0.39

0.30

355

0.41

0.31

369

0.43

0.33

392

LEGEND

Bhp

Brake Horsepower Input to Fan

ESP

External Static Pressure (in. wg)

FIOP

Factory-Installed Option

Watts — Input Watts to Motor

NOTES:
1. Values include losses for filters, unit casing, and wet coils. See

page 47 for accessory/FIOP static pressure information.

2. Extensive motor and electrical testing on these units ensures that the

full range of the motor can be utilized with confidence. Using

your fan motors up to the wattage ratings shown will not result in nui-
sance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.

3. Use of a field-supplied motor may affect wire sizing. Contact your lo-

cal representative for details.

4. Minimum allowable cfm is 300 cfm/ton.

558D036 (3 TON)

Airflow

(Cfm)

Alternate Belt-Drive Motor

External Static Pressure (in. wg)

0.1

0.2

0.3

0.4

0.5

0.6

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

900

526

0.06

70

584

0.08

99

656

0.12

139

734

0.22

219

818

0.25

269

875

0.27

289

1000

570

0.09

109

627

0.13

149

738

0.19

189

800

0.26

259

848

0.29

288

895

0.31

308

1100

614

0.13

149

670

0.16

189

758

0.23

229

812

0.29

288

863

0.32

308

914

0.35

348

1200

658

0.16

189

710

0.23

229

780

0.28

279

840

0.32

318

889

0.36

358

938

0.40

398

1300

703

0.20

239

752

0.27

269

808

0.32

318

868

0.37

368

916

0.41

408

963

0.45

448

1400

725

0.29

288

776

0.31

308

845

0.38

378

891

0.42

418

937

0.47

467

983

0.51

507

1500

755

0.33

328

816

0.38

378

870

0.43

428

924

0.48

477

969

0.53

527

1014

0.58

577

558D036 (3 TON) (cont)

Airflow

(Cfm)

Alternate Belt-Drive Motor

External Static Pressure (in. wg)

0.7

0.8

0.9

1.0

1.1

1.2

Rpm

Bhp

Watt

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

900

924

0.32

308

953

0.35

348

989

0.38

388

1028

0.42

438

1074

0.49

487

1120

0.54

537

1000

936

0.35

348

977

0.39

388

1020

0.44

438

1064

0.48

477

1124

0.54

537

1185

0.60

597

1100

960

0.39

388

1005

0.43

428

1052

0.49

487

1100

0.52

527

1163

0.59

587

1225

0.65

647

1200

960

0.45

388

1038

0.50

497

1076

0.53

527

1136

0.59

577

1201

0.65

647

1266

0.72

716

1300

1012

0.51

507

1061

0.56

557

1090

0.61

607

1172

0.65

647

1239

0.72

716

1306

0.79

786

1400

1027

0.56

557

1071

0.60

597

1108

0.67

666

1208

0.70

706

1278

0.79

786

1347

0.87

865

1500

1056

0.63

627

1097

0.68

676

1117

0.70

696

1245

0.74

776

1315

0.87

865

1385

0.96

955

LEGEND

Bhp

Brake Horsepower Input to Fan

FIOP

Factory-Installed Option

Watts — Input Watts to Motor

NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 4.)
2. Maximum usable watts input is 1000 and maximum continuous bhp

is 1.00. Extensive motor and electrical testing on these units ensures
that the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in

nuisance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.

3. Values include losses for filters, unit casing, and wet coils. See

page 47 for accessory/FIOP static pressure information.

4. Motor drive range: 760 to 1000 rpm. All other rpms require field-

supplied drive.

5. Interpolation is permissible. Do not extrapolate.
6. Use of a field-supplied motor may affect wire sizing. Contact your lo-

cal representative for details.

7. Minimum allowable cfm is 300 cfm/ton.

34