AIR DELIVERY — 559F180-300 UNITS (cont)

559F300 (25 TON)

Airflow

(Cfm)

Standard Belt-Drive Motor

External Static Pressure (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

7,000

832

2.49

2297

916

2.86

2634

993

3.23

2978

1065

3.62

3332

1134

4.01

3,697

1200

4.43

4,076

7,500

881

3.00

2761

961

3.39

3119

1035

3.78

3483

1104

4.19

3855

1170

4.60

4,237

1233

5.03

4,631

8,000

930

3.57

3284

1007

3.98

3664

1077

4.40

4049

1144

4.82

4440

1207

5.25

4,840

1268

5.70

5,249

8,500

980

4.20

3873

1053

4.64

4274

1121

5.08

4679

1185

5.53

5090

1246

5.98

5,508

1305

6.44

5,934

9,000

1030

4.92

4528

1100

5.38

4951

1166

5.84

5377

1228

6.31

5808

1286

6.78

6,244

1343

7.26

6,689

9,500

1081

5.70

5254

1148

6.19

5700

1211

6.67

6146

1271

7.16

6597

1328

7.66

7,053

1383

8.16

7,515

10,000

1132

6.57

6055

1197

7.08

6523

1257

7.59

6991

1315

8.10

7462

1370

8.62

7,937

1423

9.14

8,418

10,500

1183

7.53

6935

1245

8.06

7425

1304

8.59

7913

1360

9.13

8404

1413

9.66

8,899

1465

10.20

9,400

11,000

1235

8.57

7896

1295

9.13

8408

1351

9.68

8918

1405

10.24

9430

1457

10.80

9,944

1507

11.36

10,465

11,250

1261

9.13

8408

1320

9.70

8932

1375

10.26

9452

1428

10.83

9974

1479

11.40

10,499

559F300 (25 TON) (cont)

Airflow

(Cfm)

Standard Belt-Drive Motor

External Static Pressure (in. wg)

1.4

1.6

1.8

Rpm

Bhp

Watts Rpm

Bhp

Watts Rpm Bhp Watts

7,000

1263

4.85

4470

1326

5.30

4880

1386 5.76

5307

7,500

1294

5.47

5038

1353

5.93

5458

1411

6.40

5893

8,000

1327

6.16

5670

1384

6.63

6102

1440

7.11

6549

8,500

1362

6.92

6371

1416

7.40

6816

1470 7.90

7215

9,000

1398

7.75

7141

1451

8.25

7602

1503 8.77

8074

9,500

1436

8.67

7985

1487

9.19

8462

10,000

1475

9.67

8905

1525 10.20

9400

10,500

1515 10.76

9907

11,000

11,250

LEGEND

Bhp

Brake Horsepower Input to Fan

FIOP

Factory-Installed Option

Watts — Watts Input to Motor

NOTES:
1. Boldface indicates field-supplied drive is required. (See Note 3.)

2.

indicates additional capability of 460-v motor.

3. Factory-shipped motor drive range is 1323 to 1579 rpm. Other rpms

require a field-supplied drive.

4. Maximum continuous bhp is 10.26 (208/230, 575 v) or 11.80 (460 v)

and maximum continuous watts are 9510 (208/230, 575 v) or
11,000 (460 v). Do not adjust motor rpm such that motor maximum
bhp and/or watts is exceeded at the maximum operating cfm.

5. Static pressure losses (i.e., economizer) must be added to external

static pressure before entering Air Delivery table.

6. Interpolation is permissible. Do not extrapolate.
7. Fan performance is based on wet coils, clean filters, and

casing losses. See page 47 for accessory/FIOP static pressure
information.

8. Extensive motor and drive testing on these units ensures that the

full horsepower and watts range of the motor can be utilized with
confidence. Using your fan motors up to the watts or bhp rating
shown will not result in nuisance tripping or premature motor failure.
Unit warranty will not be affected.

9. Minimum allowable cfm is 280 cfm/ton in cooling.

10. Use of a field-supplied motor may affect wire sizing. Contact your

local representative for details. For additional information on motor
performance, refer to Evaporator-Fan Motor Performance table on
page 62.

NOTE: The 389210-201 high static regain adapter accessory may
be used to provide horizontal supply/return.

NOTE: The 389210-201 horizontal supply/return adapter accessory
improves 559F180-300 fan performance by increasing external
static pressure by amount shown above.

559F180-300 Horizontal Supply/Return Fan Performance

With 389210-201 High Static Regain Adapter Curb

46