ELECTRICAL DATA — 558D090-150 (cont)

UNIT
558D

NOMINAL

V-PH-Hz

IFM

VOLTAGE

RANGE

COMPR

(ea)

OFM

IFM

ELECTRIC

HEAT*

POWER SUPPLY

DISCONNECT

SIZE†

Min

Max

RLA

LRA

Qty

Hp

FLA

FLA

Nom kW**

FLA

MCA

MOCP††

FLA

LRA

150

(12

1

2

Tons)

208/230-3-60

Std

187

254

22.3

142.0

2

1

4

1.4

10.6

63.6/ 63.6

70/ 70

67/ 67

375/375

7.8/10.4

21.7/ 25.0

63.6/ 63.6

70/ 70

67/ 67

12.0/16.0

33.4/ 38.1

63.6/ 63.6

70/ 70

67/ 67

24.0/32.0

66.7/ 74.2

96.6/109.5

100/110

89/101

31.8/42.4

88.4/102.0

123.7/140.8

125/150

114/129

37.5/50.0

104.2/120.3

143.5/133.5

150/150

132/151

Alt

15.0

68.0/ 68.0

80/ 80

72/ 72

398/398

7.8/10.4

21.7/ 25.0

68.0/ 68.0

80/ 80

72/ 72

12.0/16.0

33.4/ 38.1

68.0/ 68.0

80/ 80

72/ 72

24.0/32.0

66.7/ 74.2

102.1/115.0

110/125

94/106

31.8/42.4

88.4/102.0

129.2/146.3

150/150

119/135

37.5/50.0

104.2/120.3

149.0/139.0

150/175

137/156

460-3-60

Std

414

508

10.4

72.0

2

1

4

0.8

4.8

29.6

40

31

190

16.5

19.8

30.8

40

31

27.8

33.4

47.8

50

44

33.0

39.7

55.6

60

51

41.7

50.2

68.7

70

63

50.0

60.1

66.1

80

75

Alt

7.4

32.2

45

34

201

16.5

19.8

34.1

45

34

27.8

33.4

51.0

60

47

33.0

39.7

58.9

60

54

41.7

50.2

71.9

80

66

50.0

60.1

69.4

80

78

575-3-60

Std

518

632

9.6

58.5

2

1

4

0.8

4.8

26.6

30

28

154

18.0

17.0

26.6

30

28

36.0

34.0

47.5

50

44

54.0

51.0

56.0

60

63

Alt

7.4

28.6

35

30

162

18.0

17.0

28.7

35

30

36.0

34.0

50.1

50

46

54.0

51.0

58.6

70

66

LEGEND AND NOTES FOR ELECTRICAL DATA TABLES ON PAGES 49-54

LEGEND

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and

575 v. Heaters are rated at 240 v, 480 v, and 575 v. If power distribution voltage
to unit varies from rated heater voltage, heater kW will vary accordingly. To de-
termine heater capacity at actual unit voltage, multiply 240 v, 480 v, or 575 v
capacity by multipliers found in Electric Heat Multiplication Factors table on
page 48.

†Used to determine minimum disconnect size per NEC.

**Heaters are field installed only.

††Fuse or HACR circuit breaker.

Fusing in single point box provides the required branch circuit protection.

NOTES:
1. In compliance with NEC requirements for multimotor and combination load

equipment (refer to NEC Articles 430 and 440), the overcurrent protective de-
vice for the unit shall be fuse or HACR breaker. The Canadian units may be
fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater
than 2%.

Use the following formula to determine the percent of voltage

imbalance.

max voltage deviation from average voltage

% Voltage Imbalance = 100 x

average voltage

EXAMPLE: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

= 457

Determine maximum deviation from average voltage.

(AB) 457 − 452 = 5 v
(BC) 464 − 457 = 7 v
(AC) 457 − 455 = 2 v

Maximum deviation is 7 v.
Determine percent of voltage imbalance.

7

% Voltage Imbalance = 100 x

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact
your local electric utility company immediately.

3. MCA calculation for units with electric heaters over 50 kW = (1.25 x IFM amps)

+ (1.00 x heater FLA).

036-150 Only

036-072 Only

090-150 Only

180-300 Only

180-300 Only

52