Sizing and placement, Dimensions - weight – Watts 15M2 User Manual
Page 2

Sizing and Placement
Rule 1 covers multiple fixture branch lines which do not
exceed 20 ft. (6m) in length.
Explanation - Fixture-unit sizing and selection table is used
to select the required PDI unit (water hammer arrestor).
Rule 2 covers multiple fixture branch lines which do exceed
20 ft. (6m) in length.
Explanation - Fixture-unit sizing and selection table is used
to select the required PDI unit (water hammer arrestor). The
sum of the fixture units rating of units X and Y shall be equal
to or greater than the demand of the branches.
X
Up to 20 ft. (6m)
Y
X
Over 20 ft. (6m)
Rule 1
Rule 2
Riser
Typical Branch Line
No. 15M2
Water Hammer Arrestor
As shown, it has been established that the preferred location
for the water hammer arrestor is at the end of the branch line
between the last two fixtures served.
The location of the water hammer arrestor shown above applies
to branch lines that do not exceed 20 ft. (6m) in length, from the
start of the horizontal branch line to the last fixture supply on
this branch line. When the branch line exceeds the 20 ft. (6m)
length, an additional water hammer arrestor should be used.
This practice is best defined by two rules which have been
established to cover the placement of water hammer arrestors.
Sizing and Selection Table
Fixture Units Sizing Information
Dimensions - Weight
Size (DN)
MODeL
ORDeR CODe
CROSS FiXTURe
UNiTS
ReF. PDi
STANDARD
in. mm
Threaded
1
⁄
2
" 15
15M2-A
0750140
1-11
A
3
⁄
4
" 20
15M2-B
0750141
12-32
B
1" 25
15M2-C
0750142
33-60
C
1" 25
15M2-D
0750143
61-113
D
1" 25
15M2-E
0750144
114-154
E
1" 25
15M2-F
0750145
155-330
F
Size (DN)
DiMeNSiONS
WeighT
A
B
in.
mm
in.
mm
(lbs)
(kgs)
Threaded
1
⁄
2
" 15M2-A
1
1
⁄
8
28.5
5
15
⁄
16
150.9
0.5
0.2
3
⁄
4
" 15M2-B
1
3
⁄
8
34.9
8
9
⁄
16
218.0
0.9
0.4
1" 15M2-C
1
5
⁄
8
41.3
8
13
⁄
16
223.5
1.3
0.6
1" 15M2-D
2
1
⁄
8
54.0
9
15
⁄
16
252.5
2.0
0.9
1" 15M2-E
2
1
⁄
8
54.0
12
11
⁄
16
322.5
2.3
1.1
1" 15M2-F
2
5
⁄
8
66.7
11
5
⁄
32
283.5
2.7
1.2
FiXTURe UNiTS
TYPe OF SUPPLY
PUBLiC
PRiVATe
FiXTURe
CONTROL
TOTAL C.W. h.W. TOTAL C.W. h.W.
Water Closet 1.66 PF
Flush Valve
8
8 –
5
5
–
Water Closet 1.66 PF
Flush Tank
5
5 –
2.5 2.5 –
Pedestal Urinal 1.06 PF
Flush Valve
4
4 –
–
–
–
Stall or Wall Urinal
Flush Valve 1.06 PF 4
4 –
–
–
–
Stall or Wall Urinal
Flush Tank 1.06 PF 2
2 –
–
–
–
Lavatory
Faucet
2 1
1
/
2
1
1
/
2
1
1
1
Bathtub
Faucet
4
2 3
2 1
1
/
2
1
1
/
2
Shower Head
Mixing Valve
4
2 3
2
1
2
Bathroom Group
Flush Valve Closet –
– –
8
8
3
Bathroom Group
Flush Tank Closet –
– –
6
6
3
Separate Shower
Mixing Valve
–
– –
2
1
2
Service Sink
Faucet
3
3 3
–
–
–
Laundry Tubs (1-3)
Faucet
–
– –
3
3
3
Combination Fixture
Faucet
–
– –
3
3
3
B
A
ES-15M2 1103