beautypg.com

Front view side view, Ustang, Eries – Watts M1115 User Manual

Page 5

background image

Size (in)

1-1/4

1-1/2

2

2-1/2

3

4

6

8

10

12

14

16

Maximum Continuous

(GPM)

95

130

210

300

485

800

1850

3100

5000

7000

8400

11100

Maximum Intermittent

(GPM)

119

161

265

390

590

1000

2300

4000

6250

8725

10500 13300

Minimum Continuous

(GPM)

1

1

1

20

30

50

115

200

300

400

500

650

12541 Gulf Freeway

Houston, Texas 77034

(Ph) 713.943.0688

(Fx) 713.944.9445

www.watts.com

M

ustang

s

eries

Model CP-15
Pressure Reducing Pilot

ITEM

NUMBER

DESCRIPTION

1

Adjusting Screw

2

Jam Nut

3

Spring Housing

4

Spring

5

Cap Screw

6

Body

7

Seat

8

O-Ring*

9

Bottom Cap

10

Spring Guide

ITEM

NUMBER

DESCRIPTION

11

Nut

12

Belleville Washer

13

Diaphragm Washer

14

Diaphragm *

15

Yoke

16

Disc and Retainer Assembly*

* Included in Repair Kit

1

2

3

10

11

16

12

13

15

14

4

6

9

7

8

5

Front View

Side View

Controls and Accessories

M115 (Globe)

M1115 (Angle)

This manual is related to the following products: