beautypg.com

Bryant Single Package Rooftop Electric Cooling/Gas Heating Units 580G User Manual

Page 7

background image

Table 2 — Evaporator Fan Motor Data

UNIT

SIZE

580G,H

MOTOR

HP

MOTOR

SHAFT

DIA.

(in.)

FAN

SHAFT
SPEED

(rpm)

MOTOR

SHEAVE

MOTOR

SHEAVE

PITCH

DIAMETER

(in.)

BUSHING

DIAMETER

(in.)

FAN

SHEAVE

FAN

SHEAVE

PITCH

DIAMETER

(in.)

BUSHING

DIAMETER

(in.)

BELT

(QUANTITY)

OUTSIDE

BELT

LENGTH

BELT

TENSION

(lb at

.24 in.)

240

5

1.12

717

BK55

4.8

None-1.125

1B5V124

12.4

B-1.9375

BX59

62

5.10

10

1.38

924

2BK50

4.4

None-1.375

2B5V86

8.6

B-1.9375

(2) BX51

54

5.21

15

1.62

1096

2B5V56

5.7

B-1.625

2B5V90

9.1

B-1.9375

(2) 5VX530

53

6.00

300

7.5

1.38

773

BK60H

5.4

H-1.375

1B5V124

12.4

B-1.9375

BX59

62

6.48

10

1.38

962

1B5V60

6.1

H-1.375

1B5V110

11.1

B-1.9375

5VX590

59

7.37

15

1.62

1106

2B5V54

5.5

B-1.625

2B5V86

8.7

B-1.9375

(2) 5VX530

53

6.12

324

10

1.38

848

2BK50

4.4

None-1.375

2B5V94

9.4

B-1.9375

(2) BX52

55

5.27

15

1.62

1059

2B5V48

4.9

B-1.625

2B5V80

8.1

B-1.9375

(2) 5VX500

50

6.63

20

1.62

1187

2B5V58

5.9

B-1.625

2B5V86

8.7

B-1.9375

(2) 5VX530

53

7.31

360

10

1.38

884

2BK50

4.4

H-1.375

2B5V90

9.0

B-1.9375

(2) BX51

54

5.24

15

1.62

1096

2B5V56

5.7

B-1.625

2B5V90

9.1

B-1.9375

(2) 5VX530

53

6.00

20

1.62

1187

2B5V58

5.9

B-1.625

2B5V86

8.7

B-1.9375

(2) 5VX530

53

7.31

NOTE: Motor shaft speed is 1750 rpm. The fan shaft diameter is 1

11

16

inches.

A. Positioning

Provide clearance around and above unit for airflow, safety,
and service access (Fig. 2 and 3).

Do not install unit in an indoor location. Do not locate air
inlets near exhaust vents or other sources of contaminated
air.

For proper unit operation, adequate combustion and ventila-
tion air must be provided in accordance with Section 5.3 (Air
for Combustion and Ventilation) of the National Fuel Gas Code,
ANSI Z223.1 (American National Standards Institute).

Although unit is weatherproof, guard against water from higher
level runoff and overhangs.

B. Roof Mount

Check building codes for weight distribution requirements.

III. FIELD FABRICATE DUCTWORK

Secure all ducts to building structure. Use flexible duct con-
nectors between unit and ducts as required. Insulate and weath-
erproof all external ductwork, joints, and roof openings with
counter flashing and mastic in accordance with applicable codes.

Ducts passing through an unconditioned space must be
insulated and covered with a vapor barrier.

To attach ductwork to roof curb, insert ductwork approx-
imately 10 to 11 in. up into the curb. Connect ductwork to
14-gage roof curb material using sheet metal screws driven
from inside the duct.

WARNING:

For vertical supply and return units, tools

or parts could drop into ductwork and cause an injury.
Install 90 degree elbow turns in the supply and return
ductwork between the unit and the conditioned space.
If a 90 degree elbow cannot be installed, then grilles of
sufficient strength and density should be installed to
prevent objects from falling into the conditioned space.

IV. UNIT DUCT CONNECTIONS

A. 580G Units

Unit is shipped for through-the-bottom duct connections. Duct-
work openings are shown in Fig. 2. Attach all ductwork to
roof curb.
Air distribution is shown in Fig. 5. Refer to
installation instructions shipped with accessory roof curb for
more information.

B. 580H Units

Remove shipping covers from supply and return air open-
ings. Attach field-supplied ductwork to unit. Use a single duct
over both return openings and a single duct over both sup-
ply openings. See Fig. 3 for duct opening dimensions. Secure
all ducts to the building structure. See Fig. 6. Use flexible
duct connectors between unit and ducts as required.

Install accessory barometric relief or power exhaust in
the field-fabricated return ductwork. Refer to Power
Exhaust/Barometric Relief Damper Hood section for more
information.

Fig. 5 — Air Distribution — Thru-the-Bottom

Fig. 6 — Air Distribution — Thru-the-Side

—7—