Table 14 — I/O Channel Designations Base Module

TERMINAL

NO.

ASSIGNMENT

T1-2

T3-4

T5-6

OAT — 5K

Thermistor

T7-8

SAT — 5K

Thermistor

T9-10

T11-12

T13-14

T15-16

T17-25

Y1 — DI (24 vac)

T18-25

Y2 — DI (24 vac)

T19-25

W1 — DI (24 vac)

T20-25

W2 — DI (24 vac)

T21-25

G — DI (24 vac)

T22-25

Compressor 1 Safety — DI (24 vac)

T23-25

Compressor 2 Safety — DI (24 vac)

T24-25

Outside Air Enthalpy — DI (24 vac)

T26-27

Economizer Pos. — AO (4-20 mA)

T28-29

Heat 1 Relay — DO (24 vac)

T30-29

Heat 2 Relay — DO (24 vac)

T31-32

CV Power Exhaust 1/Modulating Pwr Exht — DO (115 vac)

T33-32

CV Power Exhaust 2 — DO (115 vac)

T34-35

Condenser Fan — DO (115 vac)

T36-35

OFC2 — DO (115 vac)

T37-38

T39-38

K1

Indoor Fan Relay — DO (HV)

K2

Compr. 1 — DO (HV)

K3

Compr. 2 — DO (HV)

LEGEND

AO

Analog Output

CV

Constant Volume

DI

Direct Input

DO

Direct Output

HV

High Voltage

K

Kilo Ohms

OAT — Outdoor Air Thermistor
OFC — Outdoor (Condenser) Fan Contactor
SAT

Supply Air Thermistor

T

Terminal

NOTE: For 4 to 20 mA signals, all even numbered terminals are negative (−) polarity and all odd
numbered terminals are positive (+) polarity.