NOTES:
1. Connect TRAN1 to H4 for 575V units.
2. Connect TRAN2 to black lead for 575V units.
3. Circuit breaker must trip amps are equal to or less than 156% FLA for CB1 and

CB2. All others are 140%.

4. If any of the original wire furnished must be replaced, it must be replaced with

Type 90 C wire or its equivalent.

5. Compressors and/or fan motors are thermally protected.
6. Three-phase motors are protected against primary single phasing conditions.

Fig. 48 — Power Schematic; 580G,H240-360 — 575-3-60