NOTES:
1. Connect TRAN1 to H4 for 460 v units. Connect to H3 for 230 v. If

208/230 v units are run with a 208 v power supply connect to H2.

2. Connect TRAN2 to black lead for 460 v units. Connect to orange

lead for 230 v units. If 208/230 v units are run with a 208 v power
supply connect to red lead.

3. Circuit breaker must trip amps are equal to or less than 156% FLA

for CB1 and CB2. All others are 140%.

4. If any of the original wire furnished must be replaced, it must be

replaced with type 90 C wire or its equivalent.

5. Compressors and/or fan motors are thermally protected.
6. Three-phase motors are protected against primary single phasing

conditions.

TABLE A

The Following Compressors Have Two

Parallel Wires Run From TB1 to the

Compressors

Compressor

Model

Voltage

Wire

Quantity

06D-537

208-230-3-60

2

TABLE B

The Following Fan Motors Have Two

Parallel Wires Run From TB1 to the Fan

Motors

Indoor

Motor

Voltage

Wire

Quantity

20 HP

208-230-3-60

2

Fig. 47 — Power Schematic; 580G,H240-360 — 208/230-3-60 and 460-3-60