1116FM (Angle) - Pressure Relief Valve

Flow Data - F1100 (Angle)

3

4

6

8

Flow Rate GPM (Water)

460

800

1800

3100

Maximum Intermittent

Flow Rate GPM (Water)

570

1000

2300

3900

Cv Factor GPM (Globe)

125

220

460

775

Cv Factor GPM (Angle)

170

280

650

1100

Valve Cover Chamber Capacity

Valve Size - Inches

3

4

6

8

fluid oz.

10

22

70

U.S. Gal

1-1/4

Valve Travel

Valve Size - Inches

3

4

6

8

Travel - Inches

3/4

1

1-1/2

2

Headloss

Maximum continuous flow based on velocity of 20 ft. per second.

Maximum intermittent flow based on velocity of 25 ft. per second.

The C

V

Factor of a value is the flow rate in US GPM at 60° F that will cause a 1 psi drop in pressure.

The factors stated are based upon a fully open valve.

C

V

factor can be used in the following equations to determine Flow (Q) and Pressure Drop (∆ P):

Q (Flow) = C

V

∆ P ∆ P (Pressure Drop) = (Q/C

V

)

2

Angle

2

3 4 5 6 789 10

20

40

60 80 100

200

500

1000

2000

5000 10000

20000

2

3

4

6

8

10

20

40

60

80

100

Pressure Drop (psi)

Flow Rate - Gallons per Minute (Water)

3

4

6