Specifications

F110-14 (Globe)

F1110-14 (Angle)

The On-Off Float Control Valve shall be a pilot operated diaphragm valve designed to open fully or close

drip-tight as commanded by the Float Control Pilot. The Float Pilot may be either valve or remote mounted.

The valve shall close drip tight when water level reaches the adjustable high-level setpoint, and open fully

when water level is below the adjustable low-level setpoint, allowing a calculated “draw-down” of water level

to increase tank circulation.

The main valve shall be a hydraulically operated, single diaphragm actuated, globe or angle pattern valve.

Y-pattern valves shall not be permitted. The valve shall contain a disc and diaphragm assembly that forms

a sealed chamber below the valve cover, separating operating pressure from line pressure. The diaphragm

shall be constructed of nylon reinforced Buna-N, and shall not seal directly against the valve seat and shall

be fully supported by the valve body and cover. Rolling diaphragm construction will not be allowed and there

shall be no pistons operating the main valve or any pilot controls.

The main valve body and cover shall be Ductile Iron ASTM A536, and all internal cast components shall be

Ductile Iron or CF8M (316) Stainless Steel. All Ductile Iron components, including the body and cover, shall

be lined and coated with an NSF 61 Certified Epoxy Coating applied by the electrostatic heat fusion process.

All main valve throttling components (valve seat and disc guide) shall be Stainless Steel. The valve body

and cover must be machined with a 360-degree locating lip to assure proper alignment.

The disc and diaphragm assembly shall contain a Buna-N synthetic rubber “Quad Seal” that is securely

retained on 3-1/2 sides by a disc retainer and disc guide. Diaphragm assemblies utilizing bolts or cap

screws for component retention will not be permitted.

The exposed portion of the Quad Seal shall contact the valve seat and seal drip-tight. The disc and diaphragm

assembly must be guided by two separate bearings, one installed in the valve cover and one concentrically

located within the valve seat, to avoid deflection and assure positive disc-to-seat contact. Center guided

valves will not be permitted. All necessary repairs shall be made from the top of the valve while the body

remains in line.

Pilot control systems for valves 3” and smaller shall contain a Flow Clean Strainer, On-Off Float Pilot, (2)

12” Float Rods and a Float Ball. Pilot control systems for 4” valves shall contain an On-Off Float Pilot, (2)

12” Float Rods, Float Ball, an external Y-Strainer and Isolation Ball Valves on all body connections. All pilot

control systems shall utilize copper tubing and brass fittings regardless of valve size.

The valve shall be Watts ACV Model F110-14 (Globe) or F1110-14 (Angle) On-Off Float Control Valve.

Other Watts ACV Float Control Valves

F110-10 / F1110-10 Modulating Float Control Valve

F110-13 / F1110-13 Modulating Float Control Valve with Pressure Sustaining Feature

F110-AS / F1110-AS Modulating Float Control Valve with Solenoid (On-Off) Feature

F110-18 / F1110-18 On-Off Float Control Valve with Pressure Sustaining Feature

910 Ops & Inst

This manual is related to the following products: