beautypg.com

Chapter 2 theory of operation, Resistor, Coolant – Bird Technologies 8730 Series User Manual

Page 15: Optional flow interlock, Optional thermal interlock (8732a only), Calorimetry

background image

3

Chapter 2

Theory Of Operation

Resistor

Bird 8730 Series Econoloads consist of a thin-film-on-ceramic resistor

immersed in externally-supplied coolant. The coolant flows directly over the

resistor instead of using an intermediate heat transfer system, reducing the

load size to a minimum. After passing over the entire length of the resistor,

the coolant leaves the load and can either be discarded or cooled in a heat

exchanger and reused.

Coolant

The load’s electrical and thermal performance is reduced by impurities or

chemical additives in the coolant, especially ones which are deposited as scale

on the resistor. This may cause the load to overheat and fail. Salt water will

have a similar effect and should not be used. For recommended coolant, refer

to "Coolant" on page 5 and to "Specifications" on page 20.

Optional Flow Interlock

A minimum coolant flow of four gallons per minute is required at all times to

dissipate the heat from RF power. When the flow rate drops below this point,

the flow switch opens causing immediate transmitter shutdown. The flow

switch is a “normally open” type, and is closed during normal operation.
After flow is restored, a time delay switch keeps the interlock open for an

additional 12 seconds. This ensures proper operation of the cooling system

before applying RF power, preventing resistor burnout.

Optional Thermal Interlock (8732A Only)

The 8732A can be supplied with an optional passive overtemperature thermo-

switch. Normally closed, it opens at a preset temperature, turning off trans-

mitter power. The temperature setting is preset at the factory for either 72 or

79 °C (162 or 175 °F). The interlock system will not permit use of the trans-

mitter until the load has reached a safe temperature.

Calorimetry

Almost all the RF power in the load is transferred to the coolant as heat.

There is no heat transfer to the outer housing of the load, leaving it at ambi-

ent temperature even at full power. The flow rate, and the difference between

the input and output coolant temperatures, can be used to calculate the power

dissipated in the load with the following formula:

where

P = Power in kilowatts

k = 0.263 for temperature in °C, 0.146 for temp. in °F

T

out

= Water temperature at the output of the load

T

in

= Water temperature at the input to the load.

F = Water flow rate in gallons per minute

P

k

T

out

T

in

(

) F

Ч

Ч

=