11

RETURN AIR TEMPERATURE

This furnace is designed for continuous return--air minimum temperature of 60_F (15_C) db or intermittent operation down to 55_F (13_C)
db such as when used with a night setback thermometer. Return--air temperature must not exceed 80_F (27_C) db. Failure to follow these

return air limits may affect reliability of heat exchangers, motors and controls.

60

80

/ 27˚C

/ 16˚C

SUPPLY AIR

A10490

MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS

POSITION

CLEARANCE

Rear

0 (0 mm)

Front (Combustion air openings in furnace and in structure)

1 in. (25 mm)

Required for service

*24 in. (610 mm)

All Sides of Supply Plenum

1 in. (25 mm)

Sides

0 (0 mm)

Vent

0 (0 mm)

Top of Furnace

1 in. (25 mm)

* Recommended

COMBUSTION--AIR PIPE FOR NON--DIRECT (1--PIPE) VENT APPLICATION

FIELD-SUPPLIED
2-IN. (51 mm) DIA.
PVC PIPE

FIELD-SUPPLIED
2-IN. (51 mm) DIA.
TIGHT RADIUS
PVC 90

°

ELBOW

12” (300 mm) Minimum

A11487

915SA