Weidmuller ITX+ - Universal signal isolator / amplifier User Manual
Page 25
25
Output Calibration
1. Measure the output current.
2. Select ‘Calibrate output’ from the ‘Device’ menu.
. Enter the calibration password.
. The mA adjustment window will open. Adjust the output to
.00 mA using the buttons shown.
Note: you can use PgUp and PgDn controls on the keyboard for
fine adjustment and
coarse adjustment.
5. Press Next when the output has settled at .00 mA.
6. Repeat the procedure for the 20.00 mA adjustment.
7. Press OK to save the changes to the instrument.
This completes the output calibration.
See also other documents in the category Weidmuller Hardware:
- ACT20X (182 pages)
- ACT20X-HDI-SDO: NAMUR pulse isolator (2 pages)
- ACT20X-SDI-HDO: Solenoid/Alarm driver (2 pages)
- G108 Ultra SlimPak (4 pages)
- G118 Ultra SlimPak (4 pages)
- G128 Ultra SlimPak (4 pages)
- G168 Ultra SlimPak (4 pages)
- G408 Ultra SlimPak (4 pages)
- G408-1000 Ultra SlimPak (4 pages)
- G418 Ultra SlimPak (4 pages)
- G428 Ultra SlimPak (4 pages)
- G438 Ultra SlimPak (4 pages)
- G448 Ultra SlimPak (4 pages)
- G468 Ultra SlimPak (4 pages)
- G478 Ultra SlimPak (4 pages)
- HS01 Heat Sink (Ultra SlimPak series) (2 pages)
- WAVE Analog 2 OLP (7 pages)
- WAVE Analog DC/DC (7 pages)
- WAVE Analog DC Alarm (10 pages)
- WAVE Analog OLP (7 pages)
- WAVE Analog PRO Bridge (9 pages)
- WAVE Analog PRO DC (15 pages)
- WAVE Analog PRO Frequency (15 pages)
- WAVE Analog PRO RTD (13 pages)
- WAVE Analog PRO Thermo (13 pages)
- DC/DC CCC DC - with voltage supply on both sides (8 pages)
- DC/DC CCC HF - with 3 way separation (5 pages)
- DC/DC CCC LP - with voltage supply on the output side (8 pages)
- DC/DC CCC LP - without additional voltage supply (8 pages)
- PT 100/2 sig conditioners for current output (14 pages)
- PT 100/2 sig conditioners for voltage output (12 pages)
- PT 100/4 signal conditioners for current output (18 pages)
- PT 100/4 signal conditioners for voltage output (14 pages)
- Thermo Signal Conditioners for current & voltage output (14 pages)
- WAVE Control: Current Monitoring Module (6 pages)
- WAVE Control: VMA Vac Voltage-Monitoring Module (9 pages)
- PMX400TMP - Display instrument for control panel (39 pages)
- PMX420SERIES - Display instrument for control panel (68 pages)
- Portacal 1000 - Instrument Calibrator (41 pages)
- Portacal 275 - Signal source and loop calibrator (32 pages)
- PTX800D - Scalable pulse and frequency counter (22 pages)
- wavePak - Configurable singal isolator-converter (28 pages)
- PU-Overvoltage in Mains Control (4 pages)
- IE-MC-VL Series - Industrial Ethernet Media Converters (14 pages)