Vicor Javelin III User Manual
Page 3
Javelin III Power Supply Operator’s Manual
Rev. 05/11/2012 Mission Power Solutions (760) 631-6846 [email protected] Pg. 3
J1-1 and J1-9 are Signal Return pins.
J1-2 is VCC +5V @ 300mA.
J1-3 is AC Power OK (+5V = True).
J1-4, 5 and 12 are not connected
J1-5 is +12V fan power.
J1-6 is +5V DC (in).
J1-7 is DC OK and J1-8 is DC OK′.
J1-10 and J1-11 are used in conjunction according to Table 2.
J1-13 is +Remote Sense and J1-14 is –Remote Sense.
J1-11
INHIBIT′
J1-10
ENABLE′
POWER SUPPLY
STATE
1
X
ON
0
0
ON
0
1
OFF
1= TTL High or Open Circuit
0= TTL Low or Closed Circuit
X= Don’t Care
Table 2. Inhibit/Enable Logic Table
Use ITT/Cannon mating connector P/N DE15PK87.
Use 20-24 AWG stranded wire.
Output Connections
Installing ring lugs on output bus bars:
When viewed from the rear, the upper left output lug
is Return and the lower right output lug is Positive.
Place ½” or smaller bolt through output lug and ring
lugs from load cables and install retaining nut.
Tighten the nut to a torque of 10 ft/lbs.
Sense Connections
The Javelin III is equipped with Auto-Sense (load sensed at output lugs if remote sense is not connected).
Connector pin J1-13 is the +Remote Sense and J1-14 is the –Remote Sense.
If Remote Sense is desired, connect pin J1-13 to the positive load connection and pin J1-14 to the negative
load connection at the point where regulation is desired.
Attach sense terminals to load using 20-24 AWG stranded, twisted pair wire.
Verify that sense lines are not cross-connected.
J1-1
Signal Return
J1-2
VCC +5V @ 300mA
J1-3
AC Power OK
J1-4
N/C
J1-5
N/C
J1-6
+5VDC (in)
J1-7
DC OK
J1-8
DC OK′
J1-9
Signal Return
J1-10 PS Enable′
J1-11 PS Inhibit′
J1-12 N/C
J1-13 +Remote Sense
J1-14 −Remote Sense
J1-15 +5VDC Return (in)
1
8
9
15
Status/Control/Sense Connector (J1)