Javelin III Power Supply Operator’s Manual

Javelin III Power Supply
AC-DC Switcher

Javelin III Power Supply “Quick Install” Instructions

The Javelin III can be mounted at either of two surfaces (top or bottom).

Use #8-32 mounting screws. Maximum penetration should not exceed
0.21″ (5.33mm).

Maintain 2” (50,8mm) clearance at either end for airflow.

Input Connections

Input Barrier Strip (TB1)

Mounting the Javelin III Power Supply

Rev. 05/11/2012 Mission Power Solutions (760) 631-6846 [email protected] Pg. 2

Input AC or DC power is applied to barrier strip TB1. See Table 1 for
single phase, DC, 3 phase/3 wire, or 3 phase/4 wire.

To connect, use #8 ring lugs with 30A rating.

Grounding stud provided for ground connection(s) to the right of TB1.

A fault-clearing device, such as a fuse or circuit breaker, with a maxi-
mum rating per Table 1 at the power supply input is required for
safety agency compliance.

1

Single Phase

2

DC

3

3 Phase/3 Wire

4

3 Phase/4 Wire

TB1-1 L1

TB1-1 +

TB1-1 A

TB1-1 A

TB1-2 L2/N TB1-2 –

TB1-2 B

TB1-2 B

TB1-3 C

TB1-3 C

TB1-4 N

Current Requirements

30A AC

30A DC

17A AC per phase 10A AC per phase

Maximum Fuse Rating

45A

45A

25A per phase

15A per phase

Table 1. AC and DC Input Connections