Vicor Javelin II User Manual
Page 3
Javelin I & II Power Supply Operator’s Manual
Output Connections
Installing ring lugs on output studs:
When viewed from the rear, the left stud is Positive and the
right stud is Return.
Remove the nut and place .312” ID ring lug over output stud.
Replace and tighten the nut to a torque of 130 in/lbs. Do Not
Over-Tighten Nuts.
DC OK/Sense Connector (J3)
The Javelin is equipped with Auto-Sense (load sensed at output studs if
remote sense is not connected).
Connector pin J3-1 is the +Remote Sense and J3-6 is the –Remote
Sense.
If Remote Sense is desired, connect pin J3-1 to the positive load con-
nection and pin J3-6 to the negative load connection. Attach load end of
sense lines at the point where regulation is desired.
J3-2 and J3-8 provide DC OK′ and DC OK signals.
J3-3 and J3-7 provide +5V VCC and +5V Return.
J3-4 and J3-9 provide paralleling signals PR1 and PR2.
J3-5 is Chassis Ground.
Use ITT/Cannon mating receptacle P/N DE9FK87 with Amp cover
shell P/N 205729-1.
Attach terminals to 20-24 AWG stranded wire.
Use 20-24 AWG stranded, twisted pair wire for sense connections.
Verify that sense lines are not cross-connected.
Rev. 05/11/2012 Mission Power Solutions (760) 631-6846 [email protected] Pg. 3
1
6
9
5
J3 Interface Pin Out
J3-1
+Remote Sense
J3-2
DC OK′
J3-3
+5V VCC
J3-4
PR2
J3-5
Chassis Ground
J3-6
─Remote Sense
J3-7
+5V Return
J3-8
DC OK
J3-9
PR1