Plugmate output connectors general information – Vicor VIPAC Array Family of DC-DC Converters Up to 750 Watts User Manual
Page 5
8
9
Suggested Wire Gauge
Function
Wire Gauge
Application
DC Input/Output Leads
#20
0 A - 3 A
#18
4 A - 6A
(PlugMate)
#16
7 A - 10 A
#14
11 A - 15 A
#12
16 A - 25 A
#10
26 A - 40 A
#8
41 A - 65 A
#6
66 A - 104 A
#4
105 A - 160 A
PlugMate Output Connectors
General Information
Vicor P/N 25073
Vicor P/N 25067
Vicor P/N 25061
PlugMate
(Factory Installed Option)
Micro PlugMate
Mini PlugMate
Maxi PlugMate
Pin #
Function
Pin # Function
1
+Vout
5
+Vout
2
+Vout
6
N/C
3
–Vout
7
SC
4
–Vout
8
–Vout
Pin #
Function
Pin #
Function
1
+Vout
10
+Vout
2
+Vout
11
+Vout
3
+Vout
12
+Vout
4
N/C
13
+S
5
N/C
14
SC
6
N/C
15
–S
7
–Vout
16
–Vout
8
–Vout
17
–Vout
9
–Vout
18
–Vout
Pin #
Function
Pin #
Function
1
+Vout
13
+Vout
2
+Vout
14
+Vout
3
+Vout
15
+Vout
4
+Vout
16
+Vout
5
+Vout
17
+Vout
6
N/C
18
+S
7
SC
19
–S
8
–Vout
20
–Vout
9
–Vout
21
–Vout
10
–Vout
22
–Vout
11
–Vout
23
–Vout
12
–Vout
24
–Vout
1
4
5
8
I
1
9
10
18
1
12
13
24
Mating Connector Amp. P/N Vicor P/N
Housing
TYC-794657-8 25056
Pin
1-106529-2
24796
Kit
25073
Mating Connector Amp. P/N Vicor P/N
Housing
TYC1-794657-8 25050
Pin
1-106529-2
24796
Kit
25067
Mating Connector Amp. P/N Vicor P/N
Housing
TYC2-794657-4 25044
Pin
1-106529-2
24796
Kit
25061
Please Note:
VIPACs that contain multiple modules configured as a single output
(paralleled for power or redundancy) MUST have their Outputs and
Sense connected to each other at the load.
Trimming
Provisions have been made on PlugMate output connectors for adding
resistors to trim the output voltage up or down. Consult the design
calculator, for Rd/Ru trim resistor values, located at vicorpower.com.
Rd = Trim Down
Ru = Trim Up
DO NOT OPERATE A PARALLEL CONFIGURATION WITH ONLY ONE MODULE CONNECTED.
Additionally one module must be designated as “Master” by having all other modules configured
as “Boosters”. Boosters are created by shorting the SC pin to –S.