Ao l, Specifications, Electric motor & fan data – Thermal Transfer Systems AOL Series User Manual
Page 3: 60 hz nema frame) hydraulic motor information, Electric motor information (50 hz iec frame), Electric motor information (aol-low noise)

AO
L
262.554.8330
www.thermaltransfer.com
52
A
IR C
O
O
L
E
D
AO
L
Specifications
Fan
Fan
motor
Full load
Frequency
nema
thermal
sound
model
Cmm
CFm
H.p.
Voltage
phase
amps 230V
(Hz)
rpm
Frame
overload
db(a) at 3 ft.
AOL-400
62.30
2200
1.0
115/208-230
1
6.0
60
(2)
3450
56C
No
97
51.68/62.30
1825/2200
1.0
208-230/460
(3)
3
3.6/3.2
50/60
2850/3450
56C
No
97
AOL-725
101.94
3600
1.5
115/208-230
1
8.5
60
(2)
3450
56C
No
100
84.95/102.94 3000/3600
1.5
208-230/460
(4)
3
4.8/4.2
50/60
2850/3450
56C
No
100
AOL-950
133.09
4700
1.5
115/208-230
1
8.6
60
(2)
1740
145TC
No
92
133.09
4700
1.5
208-230/460
3
4.6
60
(2)
1740
145TC
No
92
AOL-1200
198.22
7000
5.0
230
1
23.00
60
(2)
1740
184TC
No
94
198.22
7000
3.0
208-230/460
3
8.8
60
(2)
1740
182TC
No
96
AOL-1600
223.70
9700
5.0
208-230/460
3
13.4
60
(2)
1740
184TC
No
98
AOL-2000
311.49
11000
7.5
230/460
3
19.6
60
(2)
1740
213TC
No
98
AOL-2500
396.44
14000
7.5
230/460
3
19.6
60
(2)
1740
213TC
No
98
AOL-3000
495.54
17500
10.0
230/460
3
24.8
60
(2)
1740
215TC
No
102
AOL-3500
495.54
17500
10.0
230/460
3
24.8
60
(2)
1740
215TC
No
102
(1)
Published electrical ratings are approximate, and may vary because of motor brand. Actual ratings are on motor nameplate.
(2)
May also be operated at 50 hz. Consult factory for details.
(3)
50 Hz voltage: 190-200-208-220/380-400-415-440
(4)
50 Hz voltage: 190-208/380-415
All motors shown are TEFC—Other motor options available upon request.
Electric Motor & Fan Data
(1)
(60 Hz Nema Frame)
Hydraulic Motor Information
motor
oil Flow
min. pressure
in
3
/reV
sound
required
required
(Cm
3
/reV)
db(a)
model
gpm (lpm)
psi (bar)
displacement
at 3 ft.
AOL-400
3.3 (12.49)
425 (29.31)
0.22 (3.6)
97
AOL-725
3.3 (12.49)
675 (46.54)
0.22 (3.6)
100
AOL-950
10.1 (38.23)
300 (20.68)
1.4 (22.94)
92
AOL-1200
10.1 (38.23)
700 (48.26)
1.4 (22.94)
94
AOL-1600
10.1 (38.23)
1100 (75.84)
1.4 (22.94)
98
AOL-2000
10.1 (38.23)
1650 (113.76)
1.4 (22.94)
98
AOL-2500
10.1 (38.23)
1650 (113.76)
1.4 (22.94)
98
AOL-3000
10.1 (38.23)
2000 (137.90)
1.4 (22.94)
102
AOL-3500
10.1 (38.23)
2000 (137.90)
1.4 (22.94)
102
Notes: Maximum Pressure is 2000 psi. Stated Minimum Operating Pressure is at Inlet
Port of Motor. 1000 psi Allowable Back Pressure.
sound
model
Cmm
CFm
KW
Voltage
phase
Frequency
rpm
Frame
db(a) at 3ft
AOL-400
51.93
1834
3.00
220/380
3
50 Hz
2800
100
81
AOL-725
84.95
3000
3.00
220/380
3
50 Hz
2800
100
84
AOL-950
110.92
3917
2.20
220/380
3
50 Hz
1410
100
83
AOL-1200
165.20
5834
5.50
220/380
3
50 Hz
1430
132
88
AOL-1600
186.44
6584
5.50
220/380
3
50 Hz
1430
132
89
AOL-2000
331.31
11700
5.00
220/380
3
50 Hz
1430
132
93
AOL-2500
331.31
11700
5.00
220/380
3
50 Hz
1430
132
93
AOL-3000
410.59
14500
5.00
220/380
3
50 Hz
1430
132
95
AOL-3500
410.59
14500
5.00
220/380
3
50 Hz
1430
132
95
Electric Motor Information (50 Hz IEC Frame)
All IEC frame motors are supplied by Sew Eurodrive and have CE mark.
Electric Motor Information (AOL-Low Noise)
sound
nema
ln
ln
ln
Frequency db(a)
model
Hp
Frame rpm CFm Cmm Voltage
(Hz)
at 3 ft.
AOL-400-1PH-LN
1
56C
1725 1100
31.15
115/230
60
71
AOL-400-3PH-LN
1
56C
1725 1100
31.15
230/460
60
71
AOL-725-1PH-LN
1.50
56C
1725 1780
50.40
115/230
60
75
AOL-725-3PH-LN
1.50
56C
1725 1780
50.40 230/460
60
75
AOL-950-3PH-LN
1.50 145TC
1160 3150
89.20 230/460
60
80
AOL-1200-3PH-LN 1.50 182TC
1160 4690 132.81 230/460
60
84
AOL-1600-3PH-LN
2
184TC
1160 6510 184.34 230/460
60
84
AOL-2000-3PH-LN
5
213TC
1160 8700 246.36 230/460
60
90
AOL-2500-3PH-LN
5
213TC
1160 11700 331.31 230/460
60
90
AOL-3000-3PH-LN
5
215TC
1160 13500 382.28 230/460
60
91
AOL-3500-3PH-LN* 10
215TC
1160 16200 458.73 230/460
60
91
Available in 60 Hz Nema Frame only.