Table 21 — Fan Performance, 548F036 High-Static Motor — Horizontal Discharge Units
LEGEND
*Motor drive range: 1075 to 1455 rpm. All other rpms require field-
supplied drive.
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Values include losses for filters, unit casing, and wet coils. See
Table 7 for accessory/FIOP static pressure information.
3. Maximum continuous bhp is 2.4 and the maximum continuous watts
are 2120. Extensive motor and electrical testing on these units
ensures that the full range of the motor can be utilized with confi-
dence. Using your fan motors up to the wattage ratings shown will
not result in nuisance tripping or premature motor failure. Unit war-
ranty will not be affected. See Indoor-Fan Motor Performance,
Table 6 for additional information.
4. Use of a field-supplied motor may affect wire sizing. Contact your
Bryant representative for details.
5. Interpolation is permissible. Do not extrapolate.
Table 22 — Fan Performance, 548F048 Standard Motor — Horizontal Discharge Units
LEGEND
NOTES:
1. Values include losses for filters, unit casing, and wet coils. See
Table 7 for accessory/FIOP static pressure information.
2. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. For additional information on motor performance, refer
to Indoor-Fan Motor Performance, Table 6.
3. Use of a field-supplied motor may affect wire sizing. Contact your
Bryant representative for details.
548F036 (3 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
Airflow
(Cfm)
External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
900
584
0.08
99
734
0.22
219
875
0.27
269
953
0.35
348
1028
0.42
438
1000
627
0.13
149
800
0.26
259
895
0.31
308
977
0.39
388
1064
0.48
477
1100
670
0.16
189
812
0.29
288
914
0.35
348
1005
0.43
428
1100
0.52
527
1200
710
0.23
229
840
0.32
318
938
0.40
398
1038
0.50
497
1136
0.59
577
1300
752
0.27
269
868
0.37
368
963
0.45
448
1061
0.56
557
1172
0.65
647
1400
776
0.31
308
891
0.42
418
983
0.51
507
1071
0.60
597
1208
0.70
706
1500
816
0.38
378
924
0.48
477
1014
0.58
577
1097
0.68
676
1245
0.74
776
548F036 (3 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
Airflow
(Cfm)
External Static Pressure (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
900
1120
0.54
537
1155
0.59
589
1186
0.64
639
1215
0.69
685
1240
0.73
730
1000
1185
0.60
597
1222
0.66
655
1255
0.71
709
1285
0.77
761
1312
0.82
811
1100
1225
0.65
647
1263
0.71
709
1298
0.77
769
1328
0.83
825
1357
0.88
879
1200
1266
0.72
716
1306
0.79
786
1341
0.86
851
1373
0.92
914
1402
0.98
973
1300
1306
0.79
786
1347
0.87
862
1383
0.94
934
1416
1.01
1003
1446
1.07
1068
1400
1347
0.87
865
1389
0.95
950
1427
1.03
1029
1461
1.11
1104
1492
1.18
1176
1500
1385
0.96
955
1428
1.05
1048
1467
1.14
1135
1502
1.22
1218
1534
1.30
1298
Bhp
— Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
548F048 (4 TONS) — STANDARD MOTOR (DIRECT DRIVE)
Airflow
(Cfm)
Low Speed
High Speed
208 v
230, 460, 575 v
208 v
230, 460, 575 v
ESP
Bhp
Watts
ESP
Bhp
Watts
ESP
Bhp
Watts
ESP
Bhp
Watts
1200
0.93
0.41
458
0.97
0.45
506
1.04
0.51
572
1.09
0.56
632
1300
0.86
0.42
471
0.90
0.46
521
0.96
0.52
589
1.02
0.58
651
1400
0.78
0.45
503
0.84
0.49
556
0.90
0.54
616
0.96
0.60
681
1500
0.73
0.47
536
0.76
0.52
593
0.83
0.56
631
0.89
0.62
698
1600
0.67
0.49
557
0.70
0.54
616
0.75
0.58
654
0.82
0.64
723
1700
0.60
0.52
584
0.63
0.57
646
0.67
0.60
678
0.74
0.66
750
1800
0.51
0.54
610
0.54
0.60
674
0.62
0.62
698
0.69
0.68
772
1900
0.40
0.56
629
0.45
0.62
696
0.54
0.64
720
0.62
0.70
796
2000
0.32
0.58
661
0.33
0.65
731
0.47
0.66
744
0.54
0.73
823
Bhp
— Brake Horsepower Input to Fan
ESP
— External Static Pressure (in. wg)
FIOP — Factory-Installed Option