Installation, Minimum clearances to combustibles – Regency Plateau PTO60 Outdoor Gas Burner User Manual
Page 10
10
Regency Plateau™ PTO30 Outdoor Gas Fireplace
INSTALLATION
Caution Requirements
The top, back and sides of the decorative gas appliance
are defi ned by standoffs. The metal ends of the
standoff may NOT be recessed into combustible
construction.
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this decorative gas
appliance be installed only in accordance with these instructions.
MINIMUM CLEARANCES TO COMBUSTIBLES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this
decorative gas appliance be installed only in accordance with these instructions.
PTO30/PT060 Clearance Requirements
E
F
Alcove
C
A
B
D
B
D
C
A
Clearance:
Dimension
Measured From:
A: Back wall
17" (432mm)
Burner to back wall
B: Sidewall
17" (432mm)
Burner to sidewall
C: Ceiling
45" (1143mm)
Burner to Ceiling
D: Unit Base
1"(25mm)
Unit Base to Combustible
E1: Alcove Width 30"
E2: Alcove Width 60"
84"(2134mm)
100" (2540mm)
Wall to Wall (Minimum)
F: Alcove Depth
60" (1524mm)
Front to Back Wall (Maximum)
Notes:
0"
No Hearth Required