10

Regency Plateau™ PTO30 Outdoor Gas Fireplace

INSTALLATION

Caution Requirements

The top, back and sides of the decorative gas appliance

are defi ned by standoffs. The metal ends of the

standoff may NOT be recessed into combustible

construction.

WARNING

Fire hazard is an extreme risk

if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this decorative gas

appliance be installed only in accordance with these instructions.

MINIMUM CLEARANCES TO COMBUSTIBLES

The clearances listed below are Minimum distances unless otherwise stated:

A major cause of fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this
decorative gas appliance be installed only in accordance with these instructions.

PTO30/PT060 Clearance Requirements

E

F

Alcove

C

A

B

D

B

D

C

A

Clearance:

Dimension

Measured From:

A: Back wall

17" (432mm)

Burner to back wall

B: Sidewall

17" (432mm)

Burner to sidewall

C: Ceiling

45" (1143mm)

Burner to Ceiling

D: Unit Base

1"(25mm)

Unit Base to Combustible

E1: Alcove Width 30"
E2: Alcove Width 60"

84"(2134mm)

100" (2540mm)

Wall to Wall (Minimum)

F: Alcove Depth

60" (1524mm)

Front to Back Wall (Maximum)

Notes:

0"

No Hearth Required