10

Regency PTO28 City Table Outdoor Gas Fireplace

INSTALLATION

AERATION ADJUSTMENT

The burner aeration is factory set but may need
adjusting due to either the local gas supply or
altitude. Open the air shutter for a blue fl ame or
close for a more yellow fl ame.

Minimum Air Shutter Opening:

Fully Closed

NG

1/2"

LP

Note: Any damage due to carboning resulting

from improperly setting the aeration
controls is NOT covered under warranty.

HIGH ELEVATION

This unit is approved for altitude 0 to 4500 ft. (CAN/
CGA 2.17-M91).

GAS LINE

INSTALLATION

Since some municipalities have additional local
codes it is always best to consult with your local
authorities and the CAN/CGA B149 installation
code.

For USA installations follow local codes and/or the
current National Fuel Gas Code, ANSI Z223.1.

When using copper or fl ex connectors use only
approved fi ttings. Always provide a union so that
gas lines can be easily disconnected for servicing.
Flare nuts for copper lines and fl ex connectors are
usually considered to meet this requirement.

NOTE: A shutoff / dante valve should be sup-
plied in or near the unit (or as per local codes)
for ease of servicing this appliance.

IMPORTANT: Always check for gas leaks with
a soap and water solution or gas leak detector.
Do not use open fl ame for leak testing.

NOTE: This is a low pressure system. Pressure
in excess of 14" will require a pressure regulator
to reduce gas fl ow to appliance.

PTO28 - NG SYSTEM DATA

Max. Supply Pressure

14" WC (3.49 kpa)

Min. Supply Pressure

5" WC (1.25 kpa)

Manifold Pressure

3.5" WC (0.87 kpa)

Orifi ce Size

#31 DMS

Maximum Input

34,000 Btu/h
(9.96 kW)

PTO28 - LP SYSTEM DATA

Max. Supply Pressure

14" WC (3.49 kpa)

Min. Supply Pressure

11" WC (2.73 kpa)

Manifold Pressure

10" WC (2.49 kpa)

Orifi ce Size

#50 DMS

Maximum Input

35,000 Btu/h
(10.26 kW)

SIT VALVE

DESCRIPTION

1. Blue push nozzle
2. Main gas outlet
3. Main gas inlet
4. Thermocouple connection

4

3

1

2

GAS PIPE PRESSURE

TESTING

The appliance must be isolated from the gas sup-
ply piping system by closing its individual manual
shut-off valve during any pressure testing of the
gas supply piping system at test pressures equal
to or less than 1/2 psig. (3.45 kPa). Disconnect
piping from valve at pressures over 1/2 psig.

The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.

Note: To properly check gas pressure, both

inlet and manifold pressures should be
checked using the valve pressure ports
on the valve.

1. Make sure the valve is in the "OFF" position.

2. Loosen the "IN" and/or "OUT" pressure tap(s),

turning counterclockwise with a

1/8"

wide

fl at screwdriver.

3. Attach manometer to "IN" and/or "OUT" pressure

tap(s) using a 5/16" ID hose.

4. Light the pilot and turn the valve to "ON" position.

5. The pressure check should be carried out with

the unit burning and the setting should be within
the limits specifi ed on the safety label.

6. When

fi nished reading manometer, turn off the

gas valve, disconnect the hose and tighten the
screw (clockwise) with a 1/8" fl at screwdriver.
Note: Screw should be snug, but do not over
tighten.