PROPANE:
NEVER CONNECT AN UNREGULATED GAS SUPPLY TO THE HEATER.
PRECAUTIONS:
• Periodically check the whole system for leaks or if the smell of gas is detected.
• Extinguish all open flames. Perform ALL leak testing outdoors.
• Never leak test while smoking.
• If you can not stop a leak, turn off the gas supply and call a qualified and licensed technician, or
your gas supplier.
• Only those parts recommended by the Manufacturer should be used. Substitution will void the
warranty.
• Do not use the heater until all connections have been leak tested and are sound !!!
GAS REQUIREMENTS:
• Maximum inlet pressure to propane regulator must not exceed 125 psi.
• A Minimum supply pressure of 11.0” w.c. is required to maintain correct burner input.
• The pressure regulator and hose assembly supplied with the appliance MUST be used. Any
replacement pressure regulator and hose must conform to standards & specifications of
the Manufacturer and all local codes.
• The installation must conform with local codes, or in the absence of local codes, with National Fuel
Gas Code.
3.2 Series 4L51/62, 44L5/6 specifications:
• Operating pressure 11” w.c.
• Inlet gas supply pressure minimum 5 psi / maximum 125 psi
• Maximum operating input rating 46,000 BTUH
• Low fire input rating 26,500 BTUH
• Effective radiant range 8 to 20 foot circle
(effected by wind and ambient temperature)
• Fuel Propane
• Net Weight 60 lbs
• Certifications CSA International US and Canada