Schwank comfortSchwank - Powder STW-JZ User Manual
Page 7
7
SPW-JZ, STW-JZ(2) / IWP, IW(2) I&O Manual
IM101229
RL: 13A
RD: MAY 2014
TABLE 1 MINIMUM CLEARANCES TO COMBUSTIBLES*
FIGURE 1 MINIMUM CLEARANCES TO COMBUSTIBLES* - refer to Table 1 for values
*The clearance to combustible materials represents the minimum distance that must be main-
tained between the heater and a nearby surface. The stated clearance to combustibles
represents a surface temperature of 90F° (50C°) above room temperature.
NOTE that in the above table the clearances are measured from the reflector.
It is the installer’s responsibility to ensure that building materials with a low heat
NOTE: A ‘PEEL & STICK’ SIGN IS SUPPLIED: USE AN INDELIBLE MARKER TO
ENTER VALUES ‘H’, ‘S’, ‘F’, & ‘B’ ON THE SIGN.
POST THE SIGN ADJACENT TO THE HEATER THERMOSTAT OR IN A
PROMINENT LOCATION.
See next page for details.
F
D
B
A
S
S
C
Suspended at an
angle up to 45°
Suspended
horizontally
C
FLOOR
H
T
H
M a x i m u m
Stack Height
H = T- C
‘T’ is meas-
ured on site,
FLOOR
T
M a x i m u m
Stack Height
H = T- C
‘T’ is meas-
ured on site,
MODELS:
SPW-JZ / IWP
STW-JZ / IW
STW-JZ2 / IW2
SUSPENDED AT AN ANGLE
UP TO 45 DEGREES
SUSPENDED
HORIZONTALLY
D
inches (cm)
B
inches (cm)
F
inches (cm)
C
inches (cm)
A
inches (cm)
S
inches (cm)
C
inches (cm)
200,000
13
(33)
6 (15.2) 74
(188)
70
(178)
14 (36)
44 (112)
76
(193)
175,000
12
(31)
6 (15.2)
72
(183)
68
(172)
13 (33)
42 (107)
74
(188)
155,000
5.5
(14)
1 (2.5)
44
(112)
64
(163)
3.5 (9)
19 (48)
64
(163)
130,000
4.5
(11)
1 (2.5)
35 (89)
60
(152)
3.3 (9)
11 (28)
60
(152)
110,000
3.5 (9)
1 (2.5)
26 (66)
54
(137)
2 (5)
10 (25)
54
(137)
80,000
3 (8)
1 (2.5)
23 (59)
38 (97)
1.75 (5)
6 (15)
38 (97)
60,000
2.5 (6)
1 (2.5)
17 (43)
34 (86)
1.5 (4)
5.5 (14)
34 (86)
45,000
2.75 (7)
1 (2.5)
24 (61)
32 (81)
2.25 (6)
7 (18)
32 (81)