beautypg.com

Input & tube kit(s) required before instalation – Schwank comfortSchwank - Powder STW-JZ User Manual

Page 46

background image

46

SPW-JZ, STW-JZ(2) / IWP, IW(2) I&O Manual

IM101229

RL: 13A

RD: MAY 2014

26. INPUT & TUBE KIT(S) REQUIRED

BEFORE INSTALATION:

ENSURE you have the CORRECT TUBE KIT(s) for the BURNER INPUT

USA - Stainless Steel Flexible Gas Connector

130,000 or less:
JL-0771-XX - 1/2”x24”

155,000 or more:
JL-0771-YY - 3/4”x36”

FLEXIBLE GAS CONNECTOR (Included in Burner Kit) - MUST INSTALL - see Section 13

CANADA - Type 1 Hose Gas Connector

130,000 or less:
JL-0771-RC - 1/2”x30”

155,000 or more:
JL-0771-RB - 3/4”x36”

CAPACITY

INPUT

(Btuh)

TUBE

LENGTH

SPW-JZ / IWP & STW-JZ / IW

ALUMINIZED STEEL TUBE KITS

(individual cartons)

STW-JZ2 / IW2

STAINLESS STEEL TUBE KITS

(individual cartons)

Tube Kit 1 #

Tube Kit 2 #

Tube Kit 1 #

Tube Kit 2 #

45,000

20'

TW-1420-JZ

-

TW-1420-JZ2

-

60,000

20'

TW-1420-JZ

-

-

-

30'

TW-1430-JZ

-

TW-1430-JZ2

-

80,000

20'

TW-1420-JZ

-

-

-

30'

TW-1430-JZ

-

TW-1430-JZ2

-

40'

TW-1040-JZ

-

TW-1040-JZ2

-

110,000

30'

TW-1430-JZ

-

-

-

40'

TW-1040-JZ

-

TW-1040-JZ2

-

50'

TW-F030-JZ TW-0020-JZ TW-F030-JZ2

TW-0020-JZ2

130,000

30'

TW-1430-JZ -

-

-

40'

TW-1040-JZ - TW-1040-JZ2 -

50'

TW-F030-JZ TW-0020-JZ TW-F030-JZ2

TW-0020-JZ2

150,000

40'

TW-1040-JZ -

-

-

50'

TW-F030-JZ TW-0020-JZ TW-F030-JZ2

TW-0020-JZ2

60'

TW-F030-JZ TW-0030-JZ TW-F030-JZ2

TW-0030-JZ2

175,000

50'

TW-1030-JZ TW-0020-JZ

-

-

60'

TW-1030-JZ TW-0030-JZ TW-1030-JZ2

TW-0030-JZ2

70'

TW-1030-JZ TW-0040-JZ TW-1030-JZ2

TW-0040-JZ2

200,000

50'

TW-1030-JZ TW-0020-JZ

-

-

60'

TW-1030-JZ TW-0030-JZ TW-1030-JZ2

TW-0030-JZ2

70'

TW-1030-JZ TW-0040-JZ TW-1030-JZ2

TW-0040-JZ2