Wiring configurations, Table 1: wiring configuration – SATEC EM720 Installation Manual User Manual
Page 12

8
Chapter 2 Installation
Wiring Configurations
There are seven wiring configurations shown in Figures 6, 7, 8, 9, 10, 11, 12 or 13;
W i r i n g C o n f i g u r a t i o n
Wiring Setup
See Figure:
3-wire 2-element direct connection using 2 CTs
3dir2
4-wire WYE 3-element using 3 (4) CTs
4Ln3 or 4LL3
4-wire WYE 3-element connection using 3 PTs, 3 CTs
4Ln3 or 4LL3
3-wire 2-element open delta connection using 2 PTs, 2 CTs
3OP2
4-wire WYE 2½-element connection using 2 PTs, 3 CTs
3Ln3 or3LL3
3-wire 2½-element open delta connection using 2 PTs, 3 CTs
3OP3
4-wire 3-element delta using 3 CTs
4Ln3 or 4LL3
Table 1: Wiring Configuration
See parameter setup instructions in the Operation Manual
Figure 6: Three Wire Using 2 CTs - Wiring Setup
:
3dir2