Wiring, Token type and configuration, Specifications – Paxton PROXIMITY panel mount HID reader User Manual
Page 2
Wiring
The declaration of conformity is available on request. Contact details are provided at:
http://paxton.info/596
This product is not suitable for retail sale. All warranties are invalid if this product is not installed by a competent person.
Token type and configuration
The reader will recognise 125 kHz HID
TM
proximity tokens in format to produce a Wiegand output (26 to 50 bit) or
EM4100 tokens to produce a Clock and Data output.
The reader scans the first token presented after power up and will match the reader mode to the format discovered.
If no token is read within 3 minutes of powering up, the reader will default to HID
TM
. If you require EM4100
operation, power cycle the reader and present an EM4100 token within 3 minutes.
Once in HID
TM
or EM4100 mode, the reader will remain in that format.
Connection to a Net2
ACU reader port
+12V DC
Red LED
Amber LED
Green LED
Clock/data1
Data/data0
Not required
0V
If used with Net2, the ACU reader port must be configured to read the correct data format.
Where Wiegand cards are used, you must set the correct data format (e.g. Wiegand 26 bits) in the ACU
reader port configuration or create a custom wiegand filter in the Net2 Server Configuration Utility. For further
information see
: AN1010 - Configuring custom Wiegand formats <
http://paxton.info/990 >
10V DC
14V DC
140 mA
115 kHz
135 kHz
- 35 °C
+ 66 °C
IPX7
40 mm
20 mm
58 mm
58 mm
17 mm
40 mm
40 mm
49 mm
49 mm
Voltage
Carrier frequency
Specifications
Operating temperature
Electrical
Environment
Dimensions
Min
Max
Width
Height
Depth
Current
Cable length
Read Range
Waterproof
Panel mount reader
Window size
Mounting holes - 3.7 mm dia - square formation
See front page for position
Max
Min
Outdoor use
3 metres
Token
Keyfob
Hands Free Token
Not Compatible