beautypg.com

Warning – Bryant 355CAV User Manual

Page 25

background image

25

Electrical Connections

See Fig. 29 for field wiring diagram showing typical field 115--v

and 24--v wiring. Check all factory and field electrical connections
for tightness.

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury or death.
Blower access door switch opens 115--v power to furnace

control. No component operation can occur. Do not bypass

or close switch with panel removed.

!

WARNING

UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent

unit operation.
Furnace control must be grounded for proper operation

or control will lock out. Control is grounded through

green/yellow wire connected to gas valve and burner

box screw.

!

WARNING

115--v Wiring

Before proceeding with electrical connections, make certain that

voltage, frequency, and phase correspond to that specified on
furnace rating plate. Also, check to be sure that service provided by

power supply is sufficient to handle load imposed by this
equipment. Refer to rating plate or Table 4 for equipment electrical

specifications.
Make all electrical connections in accordance with National

Electrical Code (NEC) ANSI/NFPA 70--2008 and any local codes

or ordinances that might apply. For Canadian installations, all
electrical connections must be made in accordance with Canadian

Electrical Code CSA C22.1 or authorities having jurisdiction.
Field--supplied wiring shall conform with the limitations of 63_F

(33_C) rise.
The furnace must be electrically grounded in accordance with local
codes; or in the absence of local codes, with the National Electric

Code ANSI/NFPA 70 and/or the Canadian Electric Code, CSA
C22.1, Part I, if an external electrical source is utilized.
Use a separate branch electrical circuit containing a properly sized

fuse or circuit breaker for this furnace. See Table 4 for wire size
and fuse specifications. A disconnecting means must be located

within sight from and readily accessible to furnace.
NOTE: Proper polarity must be maintained for 115--v wiring. If
polarity is incorrect or furnace is not grounded properly, furnace
control status code indicator light will flash rapidly and furnace
will NOT operate.

FIRE HAZARD
Failure to follow this warning could result in personal injury,

death, or property damage.
Do not connect aluminum wire between disconnect switch

and furnace. Use only copper wire. (See Fig. 30.)

!

WARNING

115-V

FIELD-SUPPLIED

DISCONNECT

SWITCH

115-V

SINGLE

PHASE

AUXILIARY

J-BOX

FURNACE

CONTROL

CENTER

TWO WIRE

24-V

TERMINAL

BLOCK

THREE-WIRE

HEATING

ONLY

FIVE

WIRE

NOTE 5

NOTE 1

NOTE

3

THERMOSTAT

TERMINALS

FIELD-SUPPLIED

DISCONNECT

CONDENSING

UNIT

R

W2

W

C

R

G

Y

GND

GND

GND

GND

FIELD 24-V WIRING

FIELD 115-, 208/230-, 460-V WIRING

FACTORY 24-V WIRING

FACTORY 115-, 208/230-, 460-V WIRING

208/230- OR

460-V

THREE PHASE

208/230-V

SINGLE

PHASE

W/W1

Y/Y2

G

C

NOTES:

1.

2.

3.

4.

5.

Connect Y or Y/Y2 terminal as shown for proper cooling operation.

Proper polarity must be maintained for 115-v wiring.

Use W2 with 2-stage thermostat when zoning.

If any of the original wire, as supplied, must be replaced, use

same type or equivalent wire.

Some thermostats require a "C" terminal connection as shown.

A98325

Fig. 29 -- Heating and Cooling Application Wiring Diagram

355C

A

V

355C

A

V