GENERATOR SHUT-DOWN PROCEDURES

NORMAL SHUTDOWN PROCEDURE

To shutdown the generator, use the following procedure:

Place both the

1.

MAIN, GFCI and LOAD circuit breakers

as shown in Figure 35 to the OFF position.

Let the engine cool by running it at low speed for 3-5

2.

minutes with no load applied.

Place the

3.

MPEC Control Switch (Figure 52) to the

OFF/RESET position.

MPEC Control Switch (Off/Reset)

Figure 52.

Verify that

4.

all the status LEDs on the MPEC display

are OFF (not lit).

Remove all loads from the generator.

5.

Inspect entire generator for any damage or loosening

6.

of components that may have occurred during
operation.

WARNING

NEVER stop the engine suddenly except in an
emergency.

EMERGENCY SHUTDOWN PROCEDURE

Place the

1.

ECU Control Switch (Figure 52) in the OFF/

Reset position.

Place

2.

MAIN, GFCI and LOAD (Figure 35) circuit

breakers in the OFF position.