beautypg.com

Installation, Connecting the ground – Multiquip GA-6HRS User Manual

Page 16

background image

pAgE 16 — ga6HR/ga6HRS 60 hz gENERATOR• OpERATiON ANd pARTs mANuAl — REv. #0 (08/12/14)

INSTAllATION

CONNECTiNg ThE gROuNd

The nut and ground terminal on the generator should always

be used to connect the generator to a suitable ground. The

ground cable should be #8 size wire (aluminum) minimum. If

copper wire is used, #10 size wire minimum should be used
At the generator, connect the terminal of the ground cable

between the lock washer and the nut (Figure 3) and tighten

the nut fully. Connect the other end of the ground cable to

a suitable earth ground (ground rod).

GA-6HR

GROUND CABLE

(#8 MINIMUM)

GROUND ROD

FOR EARTH GROUND

REFERENCE

NEC 250-52(C)

CONNECT TO

BUILDING GROUND

IF REQUIRED

GENERATOR

GROUND LUG

8 FT.

MINIMUM

Figure 3. Generator Grounding